Connecting the inverters
Kostal Pico and Solar factory Convert T inverter (RS485)
Solar-Log
1000/500/200
Installation 53 of 268
Connecting the inverters to each other (Solar-Log
500
, Solar-Log
1000
)
Connect using a 3 wire, shielded data cable.
Where to connect: Terminal strip inside the inverter
Procedure
1 Open the inverter as described in the inverter instructions.
2 Connect terminals A, B and GND of inverter 1 to the corresponding termi-
nals on inverter 2.
3 Connect the other inverters to each other in the same way.
4 Terminate in the last inverter in accordance with the inverter instructions.
5 Close inverters.
Allocating communication address
Recommendation: Continuous numbering starting with 1.
Setting: Using the inverter operating display
Procedure: As set out in the inverter's instructions