VLT® 8000 AQUAOperating Instructions
VLT®8000 AQUA Use on isolated mainsSee section RFI Switch regarding use on isolated mains.It is important to follow the recommendations regardinginst
VLT®8000 AQUAFunction:Setting of the desired operating mode when themains voltage is reconnected.Description of choice:Auto restart [0] is selected if
VLT®8000 AQUAProgramming Load and motor 100-124This parameter group allows the configurationof regulation parameters and the choice oftorque characte
VLT®8000 AQUATor q u e. CT operation is achieved by maintaining aconstant U/f ratio over the operating range.NB!:It is important that the values set i
VLT®8000 AQUAProgramming) Global factory setting different from NorthAmerican factory setting.Function:Select the rated motor frequency fM,N.Descripti
VLT®8000 AQUA- AMA can only be carried out if the rated motorcurrent of the motor is min. 35% of the ratedout-put current of the frequency converter.N
VLT®8000 AQUAProgrammingDescription of choice:Adjust the damping percentage until the motorresonance has disappeared.110 High break-away torque(HIGH S
VLT®8000 AQUA114 DC braking current(DC BRAK E CURRENT)Value:✭ 50 %The maximum value depends on the ratedmotor current. If the DC braking current isact
VLT®8000 AQUAProgrammingSelect Thermistor trip [2] if cutting out (trip) is desiredwhen the connected thermistor overheats.Select ETR Warning 1-4, if
VLT®8000 AQUAMotor size Change-over0.5kW-7.5kW >10Hz11 kW - 45 kW >5 Hz55 kW - 355 kW >3-4 Hz121 Slip compensation(SLIP COMPENSAT.)Value:-500
VLT®8000 AQUAProgramming124 Stator reactance(STATOR R EACT.)Value:✭depends on the choice of motorFunction:After setting motor data in parameters 102-1
VLT®8000 AQUAIntroduction Introduction to O perating InstructionsThese Operating Instructions are divided into foursections with information about VL
VLT®8000 AQUA References and Limits 200-228In this parameter group, the frequency and referencerange of the frequency converter are established.This
VLT®8000 AQUAProgramming Reference handlingReference handling is shown in the blockdiagram underneath.The block diagram shows how a change in a param
VLT®8000 AQUA203 Reference site(REFERENCE SITE)Value:✭Hand/Auto linked reference(LINKED TO HAND/AUTO)[0]Remote reference (REMOTE)[1]Local reference (L
VLT®8000 AQUAProgramming206 Ramp-up time(RAMP UP TIME)Value:1 - 3600 sec.✭ Depends on the unitFunction:The ramp-up time is the acceleration time from
VLT®8000 AQUA Reference typeThe example shows how the resulting reference iscalculated when Preset references are used togetherwith Sum and Relative
VLT®8000 AQUAProgrammingNB!:If Sum or Relative is selected, one of thepreset references will always be active. If thepreset references are to be witho
VLT®8000 AQUASee also parameter 216 Frequency bypass, bandwidth.221 Warning: Low current, ILOW(WARN. LOW CURR.)Value:0.0 - par. 222 Warning: High curr
VLT®8000 AQUAProgrammingThe warning functions in parameters 221-228 arenot active during ramp-up after a start command,ramp-down after a stop command
VLT®8000 AQUAto generate a warning signal via terminal 42 or45 and via the relay outputs.In Closed loop, the unit for the feedback is programmedin par
VLT®8000 AQUAProgrammingparam. 419 ) and continues operation in standard(normal) "closed loop" mode.NB!:The pipe fill closed loop operation
VLT®8000 AQUA Control principleA frequency converter rectifies AC voltage frommains into DC voltage, after which this DCvoltage is converted into a A
VLT®8000 AQUA Inputs and outputs 300-328In this parameter group, thefunctions that relate to theinput and output terminalsof the frequency convertera
VLT®8000 AQUAProgrammingDigital inputs Terminal no. 16 17 18 19 27 29 32 33parameter 300 301 302 303 304 305 306 307Value:No function (NO OPERATION) [
VLT®8000 AQUAbrake current and 115 DC braking time is different from0. Logic ‘0’ implements DC braking. See DC braking.Safety interlock has the same f
VLT®8000 AQUAProgrammingactive, the frequency converter will always be inOpen loop [0], regardless of the selection madein parameter 100 Configuration
VLT®8000 AQUA Analog inputsTwo analog inputs for voltage signals (terminals 53 and54) are provided for reference and feedback signals.Furthermore, an
VLT®8000 AQUAProgramming309 Terminal 53, min. scaling(AI 53 SCALE LOW)Value:0.0 - 10.0 V✭ 0.0 VFunction:This parameter is used for setting the signal
VLT®8000 AQUA315 Terminal 60, min. scaling and in parameter316 Terminal 60, max. scaling.315 Terminal 60, min. scaling(AI 60 SCALE LOW )Value:0.0 - 20
VLT®8000 AQUAProgramming Analog/digital outputsThe two analog/digital outputs (terminals 42 and45) can be programmed to show the present statusor a p
VLT®8000 AQUADescription of choice:No function Selected if the frequency converteris not to react to signals.Drive ready The frequency converter contr
VLT®8000 AQUAProgrammingExternal RefMIN- RefMAX0-20 mA andExternal RefMIN- RefMAX4-20 mA andExternal R efMIN-RefMAX0-32000 p whichgenerates an outp
VLT®8000 AQUAIntroduction• Energy savings in a constant air volume system• Compensation in the oversynchronousworking range• Reduces acoustic motor no
VLT®8000 AQUA322 Terminal 45, output, pulse scaling(AO 45 PULS SCALE)Value:1 - 32000 Hz✭ 5000 HzFunction:This parameter allows scaling of the pulse ou
VLT®8000 AQUAProgrammingIf the parameter 556 Bus time interval functionbecomes active, relay 1 and relay 2 will become cut offif they are activated vi
VLT®8000 AQUA323 Relay 1, output function(RELAY1 FUNCTION)Function:This output activates a relay switch. Relay switch01 can be used for indicating sta
VLT®8000 AQUAProgramming Application functions 400-434Includes this parameter group, the special functionsof the frequency converter PID regulation,
VLT®8000 AQUA Sleep modeSleep mode makes it possible to stop the motorwhen it is running at low speed, similar to a noload situation. If consumption
VLT®8000 AQUAProgramming403 Sleep mode timer(SLEEP MODE TIMER)Value:0 - 300 sec.(OFF)✭ OFFFunction:This parameter enables the frequency converter tost
VLT®8000 AQUANB!:Switching frequencies higher than 4.5 kHzimplement automatic derating of the maximumoutput of the frequency converter. SeeDerating of
VLT®8000 AQUAProgrammingFunction:Select the function which is to be activatedwhen the frequency converter is exposed toan overtemperature condition.De
VLT®8000 AQUA415 Units relating to closed loop(REF. / FDBK. UNIT)No unit [0] °C [21]✭% [1] GPM [22]rpm [2] gal/s [23]ppm [3] gal/min [24]pulse/s [4] g
VLT®8000 AQUAProgramming PID for process controlThe PID controller maintains a constant processcondition (pressure, temperature, flow, etc.) andadjus
VLT®8000 AQUA Example of application - Constant pressureregulation in water supply systemThe demand for water from waterworks varies considerably dur
VLT®8000 AQUAStart-up condi tionsIn some applications, optimum setting of the processregulator will mean that it takes an exces-sive timefor the requi
VLT®8000 AQUAProgramming PID overviewThe block diagram below shows reference andsetpoint in relation to the feedback signal.As can be seen, the remot
VLT®8000 AQUA1 setpoint a nd 1 feedb ackIf only 1 setpoint and 1 feedback signal are used,parameter 418 Setpoint 1 will be added to the remotereferenc
VLT®8000 AQUAProgramming417 Feedback function(2 FEED BACK, CALC.)Value:Minimum (MINIMUM)[0]✭Maximum (MAXIMUM)[1]Sum (SUM)[2]Difference (DIFFERENCE)[3]
VLT®8000 AQUAThe setpoint can be offset with digital, analog orbus signals, see reference handling.Used in Closed loop [1] parameter 100 Configuration
VLT®8000 AQUAProgrammingUsed in Closed loop [1] (parameter 100).Description of choice:Quick regulation is obtained by a high gain, but if thegain is t
VLT®8000 AQUA433 Motor Alternation Time(MOTOR ALT. TIME)Value:0 (OFF) - 999 hrs✭ OFFFunction:This is the time that sets the length of time betweenmoto
VLT®8000 AQUAProgramming Enhanced Sleep ModeUsing the frequency for initiating sleep-mode isacceptable in many cases, but if the suction pressureis v
VLT®8000 AQUA• Dry run protection. Shuts down at no or low flowand protects the motor and pump from overheating.• Improved energy savings with Enhance
VLT®8000 AQUAProgramming466 Maximum Pump Frequency(PUMP MAX. FREQ)Value:Value par. 201 fMIN- par. 202 fMAX(Hz)✭ 50Function:This parameter is linked to
VLT®8000 AQUAIntroduction PC software and serial communicationDanfoss offers various options for serial communication.Using serial communication, it
VLT®8000 AQUAnot be able to reset (automatically or manually) adry run trip before the timer has expired.472 Boost Time-Out(BOOST TIMEOUT)Value:0 (DIS
VLT®8000 AQUAProgramming Serial communication for FC protocol ProtocolsAs standard, all VLT 8000 AQUA units have a RS 485port which enables a choice
VLT®8000 AQUAPause time, min.: 2 charactersResponse time, min.: 2 charactersResponse time, max.: 20 msec.The time between individual characters in a t
VLT®8000 AQUAProgramming Data character (byte)The build-up of data blocks depends on the type oftelegram. There are three types of telegram and thete
VLT®8000 AQUAIf the command cannot be carried out, the slavewill send this reply (0111) Command cannot beexecuted and give the following error message
VLT®8000 AQUAProgrammingThe index character is used to indicate whetherthe command in question is a read or writecommand. For a read command, the inde
VLT®8000 AQUAConversion:The different attributes for each parameter can be seenin the section on factory settings. Since a parametervalue can only be
VLT®8000 AQUAProgramming Control word according to FC protocolThe control word is used for transmitting commandsfromamaster(e.g. aPC)toaslave.Bit Bit
VLT®8000 AQUAto disconnect the control word if it is not to be used inconnection with updating or reading of parameters.Bit 11, Relay 1:Bit 11 = "
VLT®8000 AQUAProgrammingBit 09, Local operation/serial communication control:Bit 09 = "0" means that OFF/STOP has been activatedon the contr
VLT®8000 AQUA LON - Local Operating NetworkLonWorks is an intelligent fieldbus system whichimproves the possibility of decentralising control,as comm
VLT®8000 AQUA Present output frequencyThe value of the present output frequency of thefrequency converter at any given time is transmittedas a 16-bit
VLT®8000 AQUAProgramming Serial communication 500-556In this parameter group, the serial communicationof the frequency converter is set up.In order t
VLT®8000 AQUA504 DC brake(DC BRAKE)Value:Digital input (DIGITAL INPUT)[0]Serial communication (SERIAL PORT)[1]Logic and (LOGIC AND)[2]✭Logic or (LOGIC
VLT®8000 AQUAProgrammingDigital input [0] Serial communication [1]Serial SerialKl.19 com.FunctionKl.19 com.Function0 0 Clockwise 0 0 Clockwise0 1 Cloc
VLT®8000 AQUALogic or [3]BusmsbBuslsbSetup/Pre-setmsbSetup/Pre-setlsbSetup no.Preset ref.no.0 0 0 0 100 0 1 200 1 0 300 1 1 40 1 0 0 201 0 1 201 1 0 4
VLT®8000 AQUAProgramming509 - 532 Data read-outValue:Parame-ter no.Description Display text Unit Updatinginterval509 Resulting reference (REFERENCE %)
VLT®8000 AQUAMotor voltage, parameter 517:Gives the voltage fed to the motor.DC link voltage, parameter 518:Gives the intermediate circuit voltage of
VLT®8000 AQUAProgramming533 Display text 1(DISPLAY TEXT ARRAY 1)Value:Max. 20 characters[XXXXXXXXXXXXXXXXXXXX]Function:Here, a text of max. 20 charact
VLT®8000 AQUADescription of choice:The output frequency of the frequency convertercan be frozen at the present value at any giventime, frozen at param
VLT®8000 AQUAProgramming Warning words 1+2 and Alarm wordWarning word, extended status word and alarm wordare shown in Hex format on the display. If
VLT®8000 AQUAIntroduction AccessoriesIP 20 bottom coverApplication optionType Description Order no.IP 4x top cover IP1)Option, VLT type 8006-8011 380
VLT®8000 AQUA Service functions 600-631This parameter group contains functions such asoperating data, data log and fault log.It also has information
VLT®8000 AQUAProgramming606 - 614 D ata logValue:Parameterno.DescriptionData log:Display text Unit Range606 Digital input (LOG: DIGITAL INP) Decimal 0
VLT®8000 AQUA615 Fault log: Error code(F. LOG: ERROR CODE)Value:[Index 1-10] Error Code: 0 - 99Function:This parameter makes it possible to see the re
VLT®8000 AQUAProgrammingFunction:In addition to its normal function, this parametercan be used for two different tests.Furthermore, it is possible to
VLT®8000 AQUA621 - 631 NameplateValue:Parameternr.DescriptionNameplate:Display text621 Unit type (DRIVE TYPE)622 Power component (POWER SECTION)623 VL
VLT®8000 AQUAProgrammingNB!:Parameters 700-711 for the relay cardare only activated if a relay option card isinstalled in the VLT 8000 AQUA.700 Relay
VLT®8000 AQUA Status messagesStatus messages appear in the 4th line of thedisplay - see example below.The left part of the status line indicates the
VLT®8000 AQUAAll about VLT 8000AQUAAutomatic Motor Adaptation completed(AMA STOP)Automatic motor adaptation has ben completed.The frequency converter
VLT®8000 AQUA List of warnings and alarmsThe table gives the different warnings and alarmsandindicates whether the fault locks the frequencyconverter
VLT®8000 AQUAAll about VLT 8000AQUA WarningsA warning will flash in line 2, while an explanationisgiveninline1.175ZA905.10DC LINK VOLTAGE LOWWARN. 6S
VLT®8000 AQUARittal Installation KitType Description Order No.Rittal TS8 enclosure for IP005)Installation kit for 1800mm high enclosure, VLT8152-8202,
VLT®8000 AQUAgiving an alarm. The frequency converter cannotbe reset until the counter is below 90%.The fault is that the frequency converter is overl
VLT®8000 AQUAAll about VLT 8000AQUAALARM 22Auto-optimisation not OK (AMA FAULT)A fault has been found during automatic motoradaptation. The text shown
VLT®8000 AQUAA choice must thus be made by pressing [CHANGEDATA] and choosing "Continue" + [OK] or "Stop" + [OK].If parameters nee
VLT®8000 AQUAAll about VLT 8000AQUA Special conditions Aggressive environmentsIn common with all electronic equipment, a frequencyconverter contains
VLT®8000 AQUA Calculation of resulting referenceThe calculation made below gives the resultingreference when parameter 210 Reference type isprogramme
VLT®8000 AQUAAll about VLT 8000AQUA Earth leakage currentEarth leakage current is primarily caused by thecapacitance between motor phases and the mot
VLT®8000 AQUA Extreme running conditionsShort circuitVLT 8000 AQUA is protected against short circuitsby means of current measurement in each of thet
VLT®8000 AQUAAll about VLT 8000AQUA Peak voltage on motorWhen a transistor in the inverter is opened,the voltage across the motor increases by adU/dt
VLT®8000 AQUA Acoustic noiseThe acoustic interference from the frequencyconverter comes from two sources:1. DC intermediate circuit coils2. Integral
VLT®8000 AQUAAll about VLT 8000AQUA Derating for ambient temperatureThe ambient temperature (TAMB,MAX) is the maximumtemperature allowed. The average
VLT®8000 AQUAIntroduction Cascade Controller OptionIn "Standard Mode", one motor is controlled bythe drive that has the Cascade Controller
VLT®8000 AQUA Derating for running at low speedWhen a centrifugal pump or a fan is controlled by a VLT8000 AQUA frequency converter, it is not necess
VLT®8000 AQUAAll about VLT 8000AQUA Air humidityVLT 8000 AQUA has been designed to meet theIEC 68-2-3 standard, EN 50178 pkt. 9.4.2.2/DIN40040, class
VLT®8000 AQUA Mains supply interference/harmonicsA frequency converter takes up a non-sinusoidalcurrent from mains, which increases the input current
VLT®8000 AQUAAll about VLT 8000AQUA CE labellingWhat is CE labelling?The purpose of CE labelling is to avoid technicalobstacles to trade within EFTA
VLT®8000 AQUA Danfoss frequency converter and CE labelingCE labelling is a positive feature when used for its originalpurpose, i.e. to facilitate tra
VLT®8000 AQUAEMC test results (Emission, Immunity)The following test results have been obtained using a system with a frequency converter (with option
VLT®8000 AQUA EMC ImmunityIn order to confirm immunity against interference from electrical phenomena, the following immunity test hasbeen made on a
VLT®8000 AQUAAll about VLT 8000AQUA Immunity, continuedBurst Surge ESD Radiated electro- Mains RF common Radiated radioBasic standard IEC 1000-4-4 IE
VLT®8000 AQUA Factory settingsPNU#ParameterdescriptionFactory setting Range Changesduringoperation4-setup Con-versionindexDatatype001 Languag e Engli
VLT®8000 AQUAAll about VLT 8000AQUA Factory settingsPNU#ParameterdescriptionFactory setting Range Changesduringoperation4-setup Con-ver-sionindexData
VLT®8000 AQUA Ordering numbers, LC filter modulesMains supply 3 x 200 - 240 VLC filter LC filter Rated current Max. output Powerfor VLT type enclosur
VLT®8000 AQUAConversion index Conversion factor74 0.12 10011001-1 0.1-2 0.01-3 0.001-4 0.0001Data typeData type shows the type and length of the teleg
VLT®8000 AQUAAll about VLT 8000AQUA Factory settingsPNU#ParameterdescriptionFactory setting Range Changesduringoperation4-setup Conver-sionindexDatat
VLT®8000 AQUA Factory settingsPNU#ParameterdescriptionFactory setting Range Changesduringoperation4-setup Conver-sionindexDatatype400 Reset function
VLT®8000 AQUAAll about VLT 8000AQUA Factory settingsPNU#ParameterdescriptionFactory setting Range Changesduringopera-tion4-setup Con-ver-sionindexDat
VLT®8000 AQUA Factory settingsPNU#ParameterdescriptionFactory setting Range Changesduringoperation4-setup Con-versionindexDatatype600 Operating data:
VLT®8000 AQUAAll about VLT 8000AQUA Option Card (for the four relay option card)PNU#ParameterdescriptionFactory setting Range Changesduringoperation4
VLT®8000 AQUA IndexAanalog inputs ... 31analog outputs:...
VLT®8000 AQUAIndexHigh voltage test... 61IIT mains...
VLT®8000 AQUATechnical data, mains supply 3 x 525 - 600 V... 43, 44Telegram build-up...
VLT®8000 AQUAIntroductionMainssupply3x690VVLTRated Current at 690VMax. outputfrequency (Hz)Powerdissipation (W)Ordering no. IP00Ordering no.IP208052 5
Rev. 2006-03-14www.danfoss.com/drives175R0894 MG83A202*MG83A202*
VLT®8000 AQUA LC filters VLT 8006-8011 380 - 480 V The drawing on the left gives the measurements of IP20 LC filters for the above-mentioned power ra
VLT®8000 AQUAIntroduction LC filters VLT 8006-8032, 200 - 240 V /8016-8062 380 - 480 VThe table and the drawing give the measurementsof IP 00 LC filt
VLT®8000 AQUA LC filter VLT 8042-8062 200-240 V /8072-8602 380 - 480 VThe table and the drawing give the measurements of IP20 LC filters. IP 20 LC fi
VLT®8000 AQUAIntroduction Harmonic filterHarmonic currents do not directly affect the electricityconsumption but has an impact on following condition
VLT®8000 AQUAPlease note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on400 V and assuming typical
VLT®8000 AQUAIntroduction Unpacking and ordering a VLT frequency converterIf you are in doubt as to which frequency converteryou have received and wh
VLT®8000 AQUA200-240 VTypeco dePosition in stringT29-10C0011-13C2011-13CN111-13C5411-13ST14-15SL14-15R016-17R116-17R316-174.0 kW/5.0 HP 8006 XXXXXX5.5
VLT®8000 AQUAIntroduction525-600 VTypecodePosition in stringT69-10C0011-13C2011-13CN111-13ST14-15R016-171.1 kW/1.5 HP 8002 XXX X1.5 kW/2.0 HP 8003 XXX
VLT®8000 AQUA ContentsIntroduction... 4Software
VLT®8000 AQUAOptional selections, 200-600 VDisplay Position: 18-19D01)Without LCPDL With LCPFieldbus option Position: 20-22F00 No optionsF10 Profibus
VLT®8000 AQUAIntroduction TYPE CODE Table/Ordering formMG.83.A2.02 - VLT is a registered Danfoss trademark29
VLT®8000 AQUA General technical dataMains supply (L1, L2, L3):Supply voltage 200-240 V units ...
VLT®8000 AQUAInstallationControl card, digital inputs:Number of programmable digital inputs ...
VLT®8000 AQUAFrequency ranges (digital output used as pulse output) ... 0-32
VLT®8000 AQUAInstallationCable lengths and cross-sections:Max. motor cable length, screened cable ...
VLT®8000 AQUAExternals:Enclosure ... IP00/Chassis, IP20/IP21/NEMA 1, IP
VLT®8000 AQUAInstallationVLT 8000 AQUA protection:• Electronic motor thermal protection against overload.• Temperature monitoring of heat-sink ensures
VLT®8000 AQUA Technical data, mains supply 3 x 200 - 240 VAccording to international requirements VLT type 8006 8008 8011Output current4)IVLT,N[A] 16
VLT®8000 AQUAInstallation Technical data, mains supply 3 x 200 - 240 VAccording to international requirements VLT type 8016 8022 8027 8032 8042 8052
VLT®8000 AQUAControl keys for parameter setup ... 84Indicator lamps ...
VLT®8000 AQUA Technical data, mains supply3x380-480VAccording to international requirements VLT type 8006 8008 8011Output current IVLT,N[A] (380-440
VLT®8000 AQUAInstallation Technical data, mains supply 3 x 380 - 480 VAccording to international requirements VLT type 8016 8022 8027 8032 8042Output
VLT®8000 AQUA Technical data, mains supply 3 x 380 - 480 VAccording to international requirements VLT type 8052 8062 8072 8102 8122Output current IVL
VLT®8000 AQUAInstallation Technical data, mains supply 3 x 380 - 480 VAccording to international requirements VLT type 8152 8202 8252 8302 8352Output
VLT®8000 AQUA Technical data, mains supply 3 x 380 - 480 VAccording to international requirements VLT type 8452 8502 8602 8652Output current IVLT,N[A
VLT®8000 AQUAInstallation Technical data, mains supply 3 x 525 - 600 VAccording to international requirements VLT type 8002 8003 8004 8005 8006 8008
VLT®8000 AQUA Technical data, mains supply 3 x 525 - 600 VAccording to international requirements 8016 8022 8027 8032 8042 8052 8062 8072Output curre
VLT®8000 AQUAInstallation Technical data, mains supply 3 x 525 - 690 VAccording to international requirements VVLT type 8052 8062 8072 8102 8122Outpu
VLT®8000 AQUA Technical data, mains supply 3 x 525 - 690 VAccording to international requirements VVLT type 8152 8202 8252 8302 8352 8402Output curre
VLT®8000 AQUAInstallation Technical data, mains supply 3 x 525 - 690 VAccording to international requirements VLT type 8502 8602 8652Output current I
VLT®8000 AQUADerating for ambient temperature ... 187Switching on the input ...
VLT®8000 AQUA FusesUL complianceTo comply with UL/cUL approvals, pre-fuses according to the table below must be used.200-240 VVLT Bussmann SIBA Litte
VLT®8000 AQUAInstallation525-600 VBussmann SIBA Littel fuse Ferraz-Shawmut8002 KTS-R3 5017906-004 KLS-R003 A6K-3R8003 KTS-R4 5017906-004 KLS-R004 A6K-
VLT®8000 AQUANonULcomplianceIf UL/cUL is not to be complied with, we recommend the above mentioned fuses or:VLT 8006-8032 200-240 V type gGVLT 8042-80
VLT®8000 AQUAInstallation Mechanical dimensionsAll the below listed measurements are in mm/inVLT type A B C a b aa/bb TypeIP 00/Chassis 200 - 240 V80
VLT®8000 AQUA Mechanical dimensionsMG.83.A2.02 - VLT is a registered Danfoss trademark52
VLT®8000 AQUAInstallation Mechanical dimensions (cont.)Type H, IP 20, IP 54Type I, IP 00Type J, IP 00, IP 21, IP 54MG.83.A2.02 - VLT is a registered
VLT®8000 AQUA Mechanical installationPlease pay attention to the requirementsthat apply to integration and field mountingkit, see the below list. The
VLT®8000 AQUAInstallation Installation of VLT 8452-8652 380-480 V andVLT 8502-8652, 525-6 90 VCompact IP 00/Chassis, IP 21/NEMA 1and IP 54/NEMA 12Coo
VLT®8000 AQUA General information about electrical installation High voltage warningThe voltage of the frequency converteris dangerous whenever the
VLT®8000 AQUAInstallation Extra protection with regard to indirect contactELCB relays, multiple protective earthing or earthing canbe used as extra p
VLT®8000 AQUA176FA145.16VLT 8000 AQUAOperating InstructionsSoftware version: 1.7xThese Operating Instructions can be used for all VLT 8000 AQUAfrequen
VLT®8000 AQUA RFI switchMains supply isolated from earth:If the frequency converter is supplied from an isolatedmains source ( IT mains) or TT/TN-S m
VLT®8000 AQUAInstallationCompact IP 20/NEMA 1VLT 8052 - 8122 380 - 480 VVLT 8027 - 8032 200 - 240 VVLT 8052 - 8072 525 - 600 VCompact IP 54/NEMA 12VLT
VLT®8000 AQUAAll enclosure typesVLT 8152-8652 380 - 480 VMG.83.A2.02 - VLT is a registered Danfoss trademark60
VLT®8000 AQUAInstallation High voltage testA high voltage test can be carried out by short-circuitingterminals U, V, W, L1,L2and L3and energizingby m
VLT®8000 AQUA EMC-correct electrical installation525-600 V units do not comply with EuropeanEMC and Low Voltage Directives.The following is a guideli
VLT®8000 AQUAInstallationMG.83.A2.02 - VLT is a registered Danfoss trademark63
VLT®8000 AQUA Earthing/Grounding of screened/armouredcontrol cablesGenerally speaking, control cables must be screened/armoured and the screen must b
VLT®8000 AQUAInstallation Electrical installation, enclosuresCompact IP 54/NEMA 12VLT 8006-8011, 380-4 80 VCompact IP 20/NEMA 1VLT 8006-8011, 380-4 8
VLT®8000 AQUACompact IP 54/NEMA 12VLT 8006-8032, 200-2 40 VVLT 8016-8072, 380-4 80 VCompact IP 20/NEMA 1VLT 8042-8062, 200-2 40 VCompact IP 00/Chassis
VLT®8000 AQUAInstallationCompact IP 20/NEMA 1VLT 8102-8122, 380-4 80 VCompact IP 54/NEMA 12VLT 8102-8122, 380-4 80 VIP 54/NEMA 12, IP 21/NEMA 1VLT 815
VLT®8000 AQUAIntroduction DefinitionsDefinitions are given in alphabetical order.AEO:Automatic Energy Optimization - function thatdynamically adjusts
VLT®8000 AQUAIP 54/NEMA 12, IP 21/NEMA 1 with disconnectand main fuseVLT 8252-8352, 380-4 80 VVLT 8252-8402, 525-6 90 VIP 00/Chassis with disconnect a
VLT®8000 AQUAInstallationCompact IP 20/NEMA 1, and IP 54/NEMA 12VLT 8006-8011, 380-4 80 VVLT 8002-8011, 525-6 00 VIP 54/NEMA 12VLT 8006-8032, 200-2 40
VLT®8000 AQUA Electrical installation, power cablesIP 00/Chassis and IP 20/NEMA 1VLT 8042-8062, 200-2 40 VIP 54/NEMA 12VLT 8042-8062, 200-2 40 VCompa
VLT®8000 AQUAInstallation Electrical installation, power cablesCompact IP 00 with disconnect and fuseVLT 8452-8652 380-480 V and VLT8502-8652, 525-69
VLT®8000 AQUACompact IP 21 / IP 54 without disconnect and fuseVLT 8452-8652 380-480 V and VLT8502-8652, 525-690 VNote: The RFI switch has no function
VLT®8000 AQUAInstallation Use of emc-correct cablesBraided screened/armoured cables are recommendedto optimise EMC immunity of the control cables and
VLT®8000 AQUA Tightening torque and screw sizesThe table shows the torque required when fittingterminals to the frequency converter. For VLT8006-8032
VLT®8000 AQUAInstallation Mains connectionMains must be connected to terminals 91, 92, 93.Nos. 91, 92, 93 Mains voltage 3 x 200-240 VL1, L2, L3 Mains
VLT®8000 AQUAProblems may arise at the start and at low rpm values ifthe motor sizes are widely different. This is because therelatively high ohmic re
VLT®8000 AQUAInstallation DC bus connectionThe DC bus terminal is used for DC back-up,with the intermediate circuit being suppliedfrom an external DC
VLT®8000 AQUAfrom the frequency converter, i.e. in a front panel,by means of the installation kit option.LSB:Least significant bit.Used in serial comm
VLT®8000 AQUA Electrical installation, control cablesTorque: 0.5 Nm (5 in-lbs)Screw size: M3.Generally speaking, control cables must be screened/armo
VLT®8000 AQUAInstallation Switches 1-4The dipswitch is located on the control card. It is usedfor serial communication and external DC supply.The swi
VLT®8000 AQUA Bus connectionThe serial bus connection in accordance with the RS485 (2-conductor) norm is connected to terminals68/69 of the frequency
VLT®8000 AQUAInstallation Connection example VLT 8000 AQUAThe diagram below gives an example of a typicalVLT 8000 AQUA installation.The mains supply
VLT®8000 AQUA Connection examples Single-pole start/stop- Start/stop using terminal 18.Parameter 302 = Start [1]- Quick-stop using terminal 27.Param
VLT®8000 AQUAInstallation 3-wire start/stop- Stop inverse by means of terminal 32.Parameter 306 = Stop inverse[14]- Latched start using terminal 18.P
VLT®8000 AQUA Control unit LCPThe front of the frequency converter featuresa control panel - LCP (Local Control Panel).This is a complete interface f
VLT®8000 AQUAInstallation[+/-] is used for selecting parametersand for changing a chosen parameter.These keys are also used to changethe local referen
VLT®8000 AQUA Display modeIn normal operation, any 4 different operating variablescan be indicated continuously: 1.1 and 1.2 and1.3 and 2. The presen
VLT®8000 AQUAInstallationoperating data names and units of operating dataare displayed. In the second line, operating data 2remains unchanged. When th
VLT®8000 AQUAIntroductionThe voltage of the frequency converteris dangerous whenever the equipmentis connected to mains. Incorrectinstallation of the
VLT®8000 AQUA Navigation between display modes175ZA697.10HAND LOCAL RUNNING0 ---- 60Display mode I40.0HzAUTO REMOTE RUNNINGFREQUENCY4
VLT®8000 AQUAInstallation Changing dataRegardless of whether a parameter has beenselected under the Quick menu or the Extendedmenu, the procedure for
VLT®8000 AQUA Quick MenuThe QUICK MENU key gives access to 12 of themost important setup parameters of the drive. Afterprogramming, the drive will, i
VLT®8000 AQUAInstallation Parameter DataEnter or change parameter dataor settings inaccordance with the following procedure.1. Press Quick Menu key.2
VLT®8000 AQUA ProgrammingUsing the [EXTEND MENU] key, itis possible to have access to allthe parameters for the frequencyconverter. Operation and Di
VLT®8000 AQUAProgrammingConnection examplesSetup chang e- Selection of Setup using terminals 32 and 33.Parameter 306 = Selection of Setup,lsb[4]Parame
VLT®8000 AQUA005 Max. value of user-defined readout(CUSTOM READOUT)Value:0.01 - 999,999.99✭ 100.00Function:This parameter allows a choice of the max.
VLT®8000 AQUAProgrammingFeedback [unit] (FEEDBACK [UNITS])[15]Motor voltage [V] (MOTOR VOLTAGE [V])[16]DC link voltage [V] (DC VOLTAGE [V])[17]Thermal
VLT®8000 AQUAthe relay is active, a "0" indicates inactive. Paramater007 uses an 8-bit word with the last two positionsnot used. Relays 6-9
VLT®8000 AQUAProgrammingFunction:This parameter decides the local reference unit.Description of choice:Choose the required unit for local reference.01