MG.28.D5.02 - VLT is a registered Danfoss trademark
195R0033
Parameter list
This list can be used for checking and
making a note of your parameter settings.
The list can be folded and placed in the
enclosed plastic folder.
Status messages
Fr
The frequency converter shows the present
output frequency in Hertz [Hz].
Io
The frequency converter shows the present
output current in Amps [A].
Uo
The frequency converter shows the present
output voltage in Volts [V].
Ud
The frequency converter shows the
intermediate circuit voltage in Volts [V].
Po
The frequency converter shows the
calculated output power in kilowatts [kW].
notrun
This message is displayed if an attempt is
made to change a parameter value, while
the motor is running. Stop the motor to
change the parameter value.
LCP
This message is shown if an LCP 2 control
unit has been installed and the [QUICK
MENU] or [CHANGE DATA] key has been
activated.
With an LCP 2 unit installed, it is only
possible to change parameters via this unit.
Err.
A warning or alarm will be shown by means
of a digit code on the display, e.g. Err
13. A warning will be shown on the
display until the fault has been corrected,
and an alarm will flash until [RESET] is
activated.
Ha
The frequency converter shows the present
Hand mode reference in Herz [Hz].
Warnings/alarm messages
The list below gives a description of the
different warnings and alarms.
After a Trip locked, the mains supply must
be disconnected and the fault must be
corrected. Connect the mains supply again
and reset the frequency converter. The
frequency converter is now ready for
operation.
A Trip can be reset manually in three
different ways:
- Via the control key [STOP/RESET]
- Via a digital input.
- Via serial communication.
The manual gives a description of the
different faults.
No. 2 Live zero fault
No. 4 Mains phase fault
No. 5 Voltage warning high
No. 6 Voltage warning low
No. 7 Overvoltage
No. 8 Undervoltage
No. 9 Inverter overload
No. 10 Motor overload
No. 11 Motor thermistor
No. 12 Current limit
No. 13 Overcurrent
No. 14 Earth fault
No. 15 Switch mode fault
No. 16 Short-circuit
No. 17 Serial communication time-out
No. 18 HPFB bus time-out
No. 33 Out of frequency range
No. 34 HPFB communication fault
No. 35 Inrush fault
No. 36 Overload temperature
Nos. 37-45 Internal faults
No. 50 AMT R
S
outside limit
No. 51 AMT fault re. nameplate data
No. 52 AMT faulty motor phase
No. 53 AMT motor too small
No. 54 AMT incorrect motor
No. 55 AMT timeout
No. 56 AMT warning during AMT
No. 99 Locked
Parameter- Selection/range Factory Setting
# description setting
001 Language [0]=English, [1]=German, [2]=French, [0]=English
[3]=Danish, [4]=Spanish, [5]=Italian
002 Local/remote [0]=Remote operation, [0]=Remote
operation [1]=Local operation operation
003 Local reference 0-f
MAX
/ Ref
MIN
-Ref
MAX
/ -Ref
MAX
- +Ref
MAX
000,000.000
004 Active Setup [0]=Factory Setup, [1]=Setup 1, [1]=Setup 1
[2]=Setup 2, [3]=Setup 3, [4]=Setup 4,
[5]=Multi Setup
005 Programming [0]=Factory Setup, [1]=Setup 1, [5]=Active Setup
Setup [2]=Setup 2, [3]=Setup 3, [4]=Setup 4,
[5]=Active Setup
006 Setup See manual [0]=No copying
copying
007 LCP copy [0]=No copying, [1]=Upload all [0]=No copying
parameters, [2]=Download all para-
meters, [3]=Download power-
independent parameters
008 Display scaling of 0.01 - 100.00 1.00
output frequency
009 Large display See manual [4]=Frequency
readout [Hz]
010 Small display See manual [1]=Reference
readout 1.1 [%]
011 Small display See manual [6]=Motor
readout 1.2 current [A]
012 Small display See manual [8]=Power [kW]
readout 1.3
013 Local control [0]=Local not active, [4]=Remote
[1]=Local control and open loop, operated control
[2]=Remote operated control and open as par. 100
loop, [3]=Local control as par. 100,
[4]=Remote operated control as par. 100
014 Local stop/Reset [0]=Not active, [1]=Active [1]=Active
015 Local jog [0]=Not active, [1]=Active [0]=Not active
016 Local reversing [0]=Not active, [1]=Active [0]=Not active
017 Local reset [0]=Not active, [1]=Active [1]=Active
of trip
018 Lock for [0]=Not locked, [1]=Locked [0]=Not locked
data change
019 Operating mode [0]=Auto restart, use saved ref. [1]=Forced stop,
at power-up, [1]=Forced stop, use saved ref. use saved ref.
local operation [2]=Forced stop, set ref. to 0
020 Lock for Hand [0]=Not active, disable [1]=Active, enable
mode
[1]=Active, enable
024 User-defined [0]=Not active, [1]=Active [0]=Not active
Quick Menu
025 Quick Menu [Index 1-20] 000
Setup Value 0-999
100 Configuration [0]=Speed regulation, open loop [0]=Speed
[1]=Speed regulation, closed loop regulation,
[3]=Process regulation, closed loop open loop
101 Torque [1]=Constant torque [1]=Constant
characteristic [2]=Variable torque, low torque
[3]=Variable torque, medium
[4]=Variable torque, high
[5]=Variable torque, low CT start
[6]=Variable torque, medium CT start
[7]=Variable torque, high CT start
[8]=Special motor characteristic
102 Motor power P
M,N
0.37-11 kW Depends on unit
103 Motor 200-240 V/380-480 V Depends on unit
voltage U
M,N
104
Motor
24-1000 Hz 50 Hz
frequency f
M,N
105 Motor 0.01-I
MAX
Depends on
current I
M,N
choice of motor
106 Rated 100-f
M,N
x 60 (max. 60000 rpm) Depends on
motor speed choice of motor
107 Automatic [0]=Optimisation off [0]=Optimisation
motor tuning [2]=Optimisation on off
108
Stator
0.000-X.XXX Depends on
resistance R
S
choice of motor
109 Stator 0.00-X.XX Depends on
reactance X
S
choice of motor
119 High start torque 0.0 - 0.5 sec. 0.0 sec.
120 Start delay 0.0-10.0 sec. 0.0 sec.
121 Start function [0]=DC hold during start delay time [2]=Coasting
[1]=DC brake during start delay time during start
[2]=Coasting during start delay time delay time
[3]=Start frequency/voltage clockwise
[4]=Start frequency/voltage in reference
direction
122 Function at stop [0]=Coasting [0]=Coasting
[1]=DC hold
123 Min. frequency 0.1 - 10.0 Hz 0.1 Hz
for activating of
function at stop
126 DC brake time 0-60 sec. 10 sec.
127 DC brake cut-in 0.0 (OFF) - par. 202. Output frequency OFF
frequency high limit, f
MAX
128 Motor thermal See manual [0]=No
protection protection
130 Start frequency 0.0-10.0 Hz 0.0 Hz
131 Voltage at start 0.0 - 200.0 V 0.0 V
Control keys
[QUICK MENU] gives access to
the parameters used in the
Quick menu. The [QUICK
MENU] key is also used if a change of a
parameter value is not to be carried out.
See also [QUICK MENU] + [+].
[CHANGE DATA] is used for
changing a setting. The
[CHANGE DATA] key is also
used for confirming the change of a
parameter setting.
[+] / [-] are used for selecting a
parameter and for changing
the chosen parameter value.
These keys are also used in
Display mode for switching
between operating variable
read-outs.
[QUICK MENU]+[+]
keys must be pressed
simultaneously to give
access to all
parameters.
[STOP/RESET] is used for
stopping the connected motor or
for resetting the frequency
converter after a trip.
[START] is used for starting the
frequency converter. Is always
active, but the [START] key
cannot override a stop command.
VLT 2800 Quick Reference Guide