Starting up
Initial startup of Solar-Log200
Solar-Log
1000/500/200
Installation 143 of 268
Inverter selection
On the Solar-Log
200
(BT), either the Bluetooth, or the RS485/422 B, or the
network interface can be selected, depending on the inverter used.
For an SMA Bluetooth inverter (available only with Solar-Log
200
BT):
1 In the SMA Bluetooth section, enter the serial number of the inverter and
click on Activate.
For inverter connection through the RS485/422 B interface:
1 In the Inverter on RS485/422-B section, select the manufacturer from the list.
For inverter connection through the router:
1 In the Inverter on network section, select the manufacturer from the list.
2 Click on Save
As soon as the settings are saved, the Solar-Log
200
automatically
starts detecting the inverter.
The inverter must be connected to the Solar-Log
200
and be feeding
into the network, so that the communication module can operate.
Once the AC converter has been detected, LED2 on the unit starts flashing.
Depending on the inverter used, this process can take between 5 seconds
and 10 minutes.
The Solar-Log is then restarted and data recording starts immediately: LED1
and LED2 are lit.
This completes the initial configuration.
Note
If inverter detection is not completed successfully, check the cable connection
between Solar-Log
200
and the inverter, and check the related installation
instructions in Section 4 “Connecting the inverters“.