VLT
®
6000 HVAC
95MG.60.B1.02 - VLT is a registered Danfoss trade mark
★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication port
Programming
224 Warning: High frequency, f
HIGH
(WARN. HIGH FREQ.)
Value:
Par. 200 Output frequency range = 0-120 Hz [0].
parameter 223 - 120 Hz ✭ 120.0 Hz
Par. 200 Output frequency range = 0-1000 Hz [1].
parameter 223 - 1000 Hz ✭ 120.0 Hz
Function:
If the output frequency is above the limit, f
HIGH
,
programmed in this parameter, the display will show a
flashing FREQUENCY HIGH.
The warning functions in parameters 221-228 are not
active during ramp-up after a start command, ramp-
down after a stop command or while stop-ped. The
warning functions are activated when the output
frequency has reached the resulting reference.
The signal outputs can be programmed to generate a
warning signal via terminal 42 or 45 and via the relay
outputs.
Description of choice:
The higher signal limit of the motor frequency, f
HIGH
,
must be programmed within the normal working
range of the frequency converter. See drawing at
parameter 221 Warning: Low current, I
LOW
.
225 Warning: Low reference, REF
LOW
(WARN. LOW REF.)
Value:
-999,999.999 - REF
HIGH
(parameter 226) ★ 0.0 Hz
Function:
When the remote reference lies under the limit,
Ref
LOW
, programmed in this parameter, the display
shows a flashing REFERENCE LOW.
The warning functions in parameters 221-228 are not
active during ramp-up after a start command, ramp-
down after a stop command or while stop-ped. The
warning functions are activated when the output
frequency has reached the resulting reference.
The signal outputs can be programmed to generate a
warning signal via terminal 42 or 45 and via the relay
outputs.
The reference limits in parameter 226 Warning: High
reference, Ref
HIGH
, and in parameter 227 Warning:
Low reference, Ref
LOW
, are only active when remote
reference has been selected.
In Open loop mode the unit for the reference is Hz,
while in Closed loop mode the unit is programmed in
parameter 415 Process units.
Description of choice:
The lower signal limit, Ref
LOW
, of the reference must be
programmed within the normal working range of the
frequency converter, provided parameter 100
Configuration has been programmed for Open loop
[0]. In Closed loop [1] (parameter 100), Ref
LOW
must
be within the reference range programmed in
parameters 204 and 205.
226 Warning: High reference, REF
HIGH
(WARN. HIGH REF.)
Value:
REF
Low
(parameter 225) - 999,999.999 ★ 50.0 Hz
Function:
If the resulting reference lies under the limit, Ref
HIGH
,
programmed in this parameter, the display shows a
flashing REFERENCE HIGH.
The warning functions in parameters 221-228 are not
active during ramp-up after a start command, ramp-
down after a stop command or while stop-ped. The
warning functions are activated when the output
frequency has reached the resulting reference.
The signal outputs can be programmed to generate a
warning signal via terminal 42 or 45 and via the relay
outputs.
The reference limits in parameter 226 Warning: High
reference, Ref
HIGH
, and in parameter 227 Warning:
Low reference, Ref
LOW
, are only active when remote
reference has been selected.
In Open loop the unit for the reference is Hz, while in
Closed loop the unit is programmed in parameter 415
Process units.