= factory setting. ( ) = parameter window text. [ ] = value for use in communication via serial communication port
Programming
NB!:
Parameters 555 Bus time interval and 556 Bus
time interval function are only active when FC
protocol [0] has been selected in parameter 500
Protocol.
555 Bus time interval (BUS TIME INTERVAL)
Value:
1 - 65534 sec. 60 sec.
Function:
In this parameter, the time is set which is expected to
pass as a maximum between the receipt of two
telegrams in a row. If this time is exceeded, the serial
communication is assumed to have stopped and the
required reaction is set in parameter 556 Bus time
interval function.
Description of choice:
Set the required time.
556 Bus time interval function
(BUS TIME INTERVAL FUNCTION)
Value:
Off (OFF) [0]
Freeze output (FREEZE OUTPUT) [1]
Stop (STOP) [2]
Jogging (JOG FREQUENCY) [3]
Max. output frequency (MAX FREQUENCY) [4]
Stop and trip (STOP AND TRIP) [5]
Function:
In this parameter, the required reaction from the VLT
frequency converter is selected when the time set in
parameter 555 Bus time interval has been exceeded.
Description of choice:
The output frequency of the VLT frequency converter
can be frozen at the present value at any given time,
frozen at parameter 211 Preset reference 1, frozen at
parameter 202 Max. output frequency, or stop and
activate a cut-out.