WARNING: 41
MOTOR TOO BIG (MOTOR TOO BIG)
The motor used is probably too big for AMA to be
carried out. The setting in parameter 102 Motor
power, P
M,N
may not match the motor. Check the
motor and choose ‘Continue’ or [STOP].
WARNING: 42
MOTOR TOO SMALL (MOTOR TOO SMALL)
The motor used is probably too small for AMA to be
carried out. The setting in parameter 102 Motor
power, P
M,N
may not match the motor. Check the
motor and select ‘Continue’ or [STOP].
ALARM: 60
Safety stop (EXTERNAL FAULT)
Terminal 27 (parameter 304 Digital inputs) has been
programmed for a Safety interlock [3] and is a logic ‘0’.
WARNING: 61
Output frequency low (FOUT < FLOW)
The output frequency is lower than parameter 223
Warning: Low frequency, f
LOW
.
WARNING: 62
Output frequency high (FOUT > FHIGH)
The output frequency is higher than parameter 224
Warning: High frequency, f
HIGH
.
WARNING/ALARM: 63
Output current low (I MOTOR < I LOW)
The output current is lower than parameter 221
Warning: Low current, I
LOW
. Select the required
function in parameter 409 Function in case of no
load.
WARNING: 64
Output current high (I MOTOR > I HIGH)
The output current is higher than parameter 222
Warning: High current, I
HIGH
.
WARNING: 65
Feedback low (FEEDBACK < FDB LOW)
The resulting feedback value is lower than
parameter 227 Warning: Low feedback, FB
LOW
.
WARNING: 66
Feedback high (FEEDBACK > FDB HIGH)
The resulting feedback value is higher than
parameter 228 Warning: High feedback, FB
HIGH
.
WARNING: 67
Remote reference low
(REF. < REF LOW)
The remote reference is lower than parameter 225
Warning: Low reference, REF
LOW
.
WARNING: 68
Remote reference high
(REF. > REF HIGH)
The remote reference is higher than parameter 226
Warning: High reference, REF
HIGH
.
WARNING: 99
Unknown fault (UNKNOWN ALARM)
An unknown fault has occurred which the software
is not able to handle.
Contact your Danfoss supplier.