Danfoss VLT 6000 HVAC Manual de servicio Pagina 123

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 177
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 122
VLT
®
6000 HVAC
123MG.60.B1.02 - VLT is a registered Danfoss trademark
Programming
Data character (byte)
The build-up of data blocks depends on the type of
telegram. There are three types of telegram and the
telegram type applies to both control telegram
(masterslave) and reply telegram (slavemaster).
The three types of telegram are the following:
1. Parameter block, used for transferring parameters
between master and slave. The data block has 12
bytes (6 words) and also contains the process
block.
PKE IND PWE
HIGH
PWE
LOW
PCD1 PCD2
Parameter block Process block
2. Process block, built up as a data block with four
bytes (2 words), covering:
- Control word and reference value
(from master to slave)
- Status word and present output frequency
(from slave to master).
PCD 1 PCD 2
Process block
3. Text block, used for reading or writing texts via the
data block.
PKE IND Ch 1 Ch2 Ch n PCD1 PCD2
Tekxt block Process block
1. Address format 1-126
The byte for the 1-126 address range has the
following profile:
76 543210
11
11
1
Bit 7 = 1 (address format 1-126 active)
Bit 0-6 = VLT frequency converter address 1-126
Bit 0-6 = 0 Broadcast
The slave sends the address byte back to the master
in the reply telegram in unchanged form.
Example:
A telegram is sent to VLT frequency converter address
22 using address format 1-31:
76 543210
00
00
0
00
00
0
00
00
0
11
11
1
00
00
0
11
11
1
11
11
1
00
00
0
Data control byte (BCC)
The data control byte can be explained by means of
an example: Before the first byte of the telegram is
received, the calculated check sum (BCS) is 0.
7 6 5 4 3 2 1 0
0 0000000
After the first byte (02H) has been received:
BCS = BCC EXOR "first byte"
(EXOR = exclusive-or gate)
BCS = 0 0 0 0 0 0 0 0
EXOR
"first byte"= 0 0 0 0 0 0 1 0 (02H)
BCC = 0 0 0 0 0 0 1 0
Each additional, subsequent byte is gated with BCS
EXOR and results in a new BCC, such as:
BCS = 0 0 0 0 0 0 1 0
EXOR
"second byte" = 1 1 0 1 0 1 1 0 (D6H)
BCC = 1 1 0 1 0 1 0 0