EMC test results (Emission, Immunity)
The following test results have been obtained using a system with a VLT frequency converter (with options if
relevant), a screened/armoured control cable, a control box with potentiometer, as well as a motor and motor
cable.
In order to minimise the cable-borne noise to the mains supply and the radiated noise from the frequency
converter system, the motor cables should be as short as possible and the screen ends should be made in
accordance with the section on electrical installation.
VLT 6016-6275/380-460 V Emission
VLT 6006-6042/200-240 VEnvironment Industrial environment Residences and light industries
Basic standard EN 55011 Class A1 EN 55011 Class B1
Setup Motor cable Cable-borne Radiated Cable-borne Radiated
150 kHz-30 MHz 30 MHz-1 GHz 150 kHz-30 MHz 30 MHz-1 GHz
300 unscreened/
VLT 6000 w/o unarmoured No No No No
RFI filter option 150 m screened/
armoured No Yes No No
VLT 6000
300 m unscreened/
with RFI filter unarmoured No No No No
(integrated) 50 m screened/
armoured Yes Yes Yes No
150 m screened/
armoured Yes Yes No No
Comment
VLT 6002-6011/380-460 V Emission
VLT 6002-6005/200-240 V Environment Industrial environment Residences and light industries
Basic standard EN 55011 Class A1 EN 55011 Class B1
Setup Motor cable Cable-borne Radiated Cable-borne Radiated
150 kHz-30 MHz 30 MHz-1 GHz 150 kHz-30 MHz 30 MHz-1 GHz
300 m unscreened/
unarmoured Yes No No No
VLT 6000 with 50 m screened/
integrated RFI filter armoured Yes Yes
Yes
1)
No
150 m screened/
armoured Yes Yes No No
VLT 6000 300 m unscreened/
with integrated unarmoured Yes No No No
RFI + LC-module 150 m screened/
armoured Yes Yes No No
Comment
1) Bookstyle 20 m screened/armoured.