Danfoss VLT 6000 HVAC Manual de servicio Pagina 41

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 177
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 40
VLT
®
6000 HVAC
41MG.60.B1.02 - VLT is a registered Danfoss trademark
Introduction to
HVAC
LC-filter IP 20
LC type A [mm] B [mm] C [mm] D [mm] E [mm] F [mm] G [mm] Weight [kg]
175Z4701 740 550 600 70
175Z4702 740 550 600 70
175Z4703 740 550 600 110
175Z4704 740 550 600 120
175Z4705 830 630 650 220
175Z4706 830 630 650 250
175Z4707 830 630 650 250
The table and the drawing give the measurements of
IP 20 LC filters. IP 20 LC filters must be integrated
and protected against dust, water and aggressive
gases.
LC filter 6075-6275 380 - 460 V
Max. motor cable length:
- 150 m screened/armoured cable
- 300 m unscreened/unarmoured cable
If EMC standards are to be complied with:
- EN 55011-1B: Max. 50 m screened/armoured cable
Bookstyle: Max. 20 m screened/armoured cable
- EN 55011-1A: Max. 150 m screened/armoured cable
Vista de pagina 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 176 177

Comentarios a estos manuales