VLT
®
6000 HVAC
MG.60.B1.02 - VLT is a registered Danfoss trademark
126
PKE
IND
PWE
HIGH
PWE
LOW
PKE
IND
PWE
HIGH
PWE
LOW
PKE
IND
PWE
HIGH
PWE
LOW
PKE
IND
PWE
HIGH
PWE
LOW
Parameter 202 Output frequency high limit, f
MAX
is to
be changed to 100 Hz. This value must be remember
after a power failure, so it is written in EEPROM.
PKE = E0CA Hex - Write to parameter 202
Output frequency high limit, f
MAX
IND = 0000 Hex
PWE
HIGH
= 0000 Hex
PWE
LOW
= 03E8 Hex - Data value 1000, corre-
sponding to 100 Hz, see Conversion.
E0CA H 0000 H 0000 H 03E8 H
The reply from the slave to the master will be:
10CA H 0000 H 0000 H 03E8 H
Example - Choice of a data value:
kW [20] is to be selected in parameter 415 Process
units. This value must be remembered after a power
failure, so it is written in EEPROM.
PKE = E19F Hex - Write to parameter 415
Process units
IND = 0000 Hex
PWE
HIGH
= 0000 Hex
PWE
LOW
= 0014 Hex - Choose data choice kW [20]
E19F H 0000 H 0000 H 0014 H
The reply from the slave to the master will be:
119F H 0000 H 0000 H 0014 H
Example - Read a parameter value:
PKE
IND
PWE
HIGH
PWE
LOW
PKE
IND
PWE
HIGH
PWE
LOW
The value in parameter 206 Ramp-up time is required.
The master sends the following enquiry:
PKE = 10CE Hex - read parameter 206
Ramp-up time
IND = 0000 Hex
PWE
HIGH
= 0000 Hex
PWE
LOW
= 0000 Hex
10CE H 0000 H 0000 H 0000 H
If the parameter value in parameter 206 Ramp-up time
is 10 seconds, the reply from the slave to the master
will be as follows:
10CE H 0000 H 0000 H 000A H