★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication port
Programming
109 Resonance damping
(RESONANCE DAMP.)
Value:
0 - 500 % ★100 %
Function:
High-frequency electric resonance problems between
the VLT frequency converter and the motor can be
eliminated by adjusting the resonance damping.
Description of choice:
Adjust the damping percentage until the motor
resonance has disappeared.
110 High break-away torque
(HIGH START TORQ.)
Value:
0.0 - 0.5 sec. ★ 0.0 sec.
Function:
In order to secure a high starting torque, the
maximum torque for max. 0.5 sec. is allowed.
However, the current is limited by the protection limit
of the VLT frequency converter (inverter).
0 sec. corresponds to no high break-away torque.
Description of choice:
Set the necessary time in which a high starting torque
is desired.
111 Start delay (START DELAY)
Value:
0.0 - 120.0 sec. ★ 0.0 sec.
Function:
This parameter enables a delay of the starting time
after the conditions for start have been fulfilled. When
the time has passed, the output frequency will start
by ramping up to the reference.
Description of choice:
Set the desired time until acceleration is to begin.
112 Motor preheater (MOTOR PREHEAT)
Value:
✭ Disable (DISABLE) [0]
Enable (ENABLE) [1]
Function:
The motor preheater ensures that no condensate
develops in the motor at stop. This function can also
be used to evaporate condensed water in the motor.
The motor preheater is only active during stop.
Description of choice:
Select Disable [0] if this function is not required.
Select Enable [1] to activate motor preheating. The
DC current is set in parameter 113 Motor preheater
DC current.
113 Motor preheater DC current
(PREHEAT DC-CURR.)
Value:
0 - 100 % ★ 50 %
The maximum value depends on the rated motor
current, parameter 105 Motor current, I
M,N
.
Function:
The motor can be preheated at stop by means of a
DC current to prevent moisture from entering the
motor.
Description of choice:
The motor can be preheated by means of a DC
current. At 0%, the function is inactive; at a value
higher than 0%, a DC current will be supplied to the
motor at stop (0 Hz). In fans that rotate because of
the air flow when they are not in operation
(windmilling), this function can also be used to
generate a holding torque.
If too high a DC current is supplied for too
long, the motor can be damaged.