VLT
®
6000 HVAC
75MG.60.B1.02 - VLT is a registered Danfoss trade mark
= factory setting. ( ) = display text [ ] = value for use in communication via serial communication port
Programming
001 Language (LANGUAGE)
Value:
English (ENGLISH) [0]
German (DEUTSCH) [1]
French (FRANCAIS) [2]
Danish (DANSK) [3]
Spanish (ESPAÑOL) [4]
Italian (ITALIANO) [5]
Swedish (SVENSKA) [6]
Dutch (NEDERLANDS) [7]
Portuguese (PORTUGUESA) [8]
State when delivered may vary from factory setting.
Function:
The choice in this parameter defines the language to
be used on the display.
Description of choice:
There is a choice of the languages indicated.
The Setup configuration
VLT 6000 HVAC has four Setups (parameter Setups)
that can be programmed independently of each other.
The active Setup can be selected in parameter 002
Active Setup. The active Setup number will be shown
in the display under "Setup".
It is also possible to set the VLT frequency converter
to Multi-Setup to allow switching of Setups with the
digital inputs or serial communication.
Setup shifts can be used in systems where, e.g., one
Setup is used during the day and another at night.
Parameter 003 Copying of Setups enables copying
from one Setup to another.
By means of parameter 004 LCP copy, all Setups can
be transferred from one VLT frequency converter to
another by moving the control panel. First all
parameter values are copied to the control panel. This
can then be moved to another VLT frequency
converter, where all parameter values can be copied
from the control unit to the VLT frequency converter.
002 Active Setup (ACTIVE SETUP)
Value:
Factory Setup (FACTORY SETUP) [0]
Setup 1 (SETUP 1) [1]
Setup 2 (SETUP 2) [2]
Setup 3 (SETUP 3) [3]
Setup 4 (SETUP 4) [4]
MultiSetup (MULTI SETUP) [5]
Function:
The choice in this parameter defines the Setup
number you want to control the functions of the VLT
frequency converter.
All parameters can be programmed in four individual
parameter Setups, Setup 1 - Setup 4.
In addition, a pre-programmed Setup called the
Factory Setup exists. This only allows specific
parameters to be changed.
Description of choice:
Factory Setup [0] contains the parameter values pre-
set at the factory. Can be used as a data source if the
other Setups are to be returned to a known state. In
this case Factory Setup is selected as the active
Setup.
Setups 1-4 [1]-[4] are four individual Setups that can
be selected as required.
MultiSetup [5] is used if remote switching between
different Setups is required. Terminals 16/17/29/32/
33 and the serial communication port can be used for
switching between Setups.
Programming
Using the [EXTEND MENU] key, it is pos-
sible to have access to all the parameters
for the VLT frequency converter.
Operation and Display 000-017
This parameter group makes it possible to set up the
control unit, e.g. with respect to language, display
readout and the possibility of making the function
keys on the control unit inactive.