Installation
■■
■■
■ Switches 1-4
The dipswitch is located on the control card.
It is used for serial communication and external DC
supply.
The switching position shown is the factory setting.
Switch 1 has no function.
Switches 2 and 3 are used for terminating an RS 485
interface, serial communication. In the first and the
last VLT frequency converter, switches 2 and 3 must
be ON. In the other VLT frequency converters,
switches 2 and 3 must be OFF.
Switch 4 is used if an external 24 V DC supply is
required for the control terminals.
Switch 4 separates the common potential for the
internal 24 V DC supply from the common potential of
the external 24 V DC supply.
NB!
Please note that when Switch 4 is in position
"OFF", the external 24 V DC supply is
galvanically isolated from the VLT frequency converter.
■■
■■
■ Electrical installation, control cables
Torque: 0.5-0.6 Nm
Screw size: M3
See page 56 for correct termination of control cables.
No. Function
Relay output 1 can be used for
indicating status and warnings.
Voltage supply to digital inputs. For the
24 V DC to be used for digital inputs,
switch 4 on the control card must be
closed, position "on".
Digital inputs. See parameters 300-307
Digital inputs.
Common for digital inputs.
Common for analogue/digital outputs.
Must be connnected to terminal 55 by
means of a three-wire transmitter. See
Examples of connection.
Analogue/digital outputs for indicating
frequency, reference, current and torque.
See parameters 319-322 Analogue/
digital outputs.
Supply voltage to potentiometer and
thermistor 10 V DC.
Analogue voltage input, 0 - 10 V DC.
Common for analogue voltage inputs.
61
68, 69
No. Function
Analogue current input 0/4-20 mA.
See parameters 314-316 Terminal 60.
Termination of serial communication.
See page 56.
This terminal is not normally to be used.
RS 485 interface, serial communication.
Where the VLT frequency converter is
connected to a bus, switches 2 and 3
(switches 1- 4 - see next page) must be
closed on the first and the last VLT
frequency converter. On the remaining
VLT frequency converters, switches 2
and 3 must be open. The factory setting
is closed (position on).
12, 13
16-33
20
39
42, 45
50
53, 54
55
04, 05
60