VLT
®
6000 HVAC
166
MG.60.B1.02 - VLT is a registered Danfoss trade mark
DM: Differential mode
CM: Common mode
CCC: Capacitive clamp coupling
DCN: Direct coupling network
1
) Injection on cable shield
2
) 2.3 x U
N
: max. test pulse 380 V
AC
: Class 2/1250 V
PEAK
, 415 V
AC
: Class 1/1350 V
PEAK
Immunity, continued
VLT
6002-6250 380-460 V, VLT
6002-6027 200-240 V
Burst Surge ESD
Radiated electro- Mains RF common Radiated radio
Basic standardBasic standard
Basic standardBasic standard
Basic standard
IEC 1000-4-4 IEC 1000-4-5 1000-4-2
magnetic field distortion mode voltage freq.elect.field
IEC 1000-4-3 VDE 0160 ENV 50141 ENV 50140
Acceptance criterion B B B A A A
Port connection CM DM CM DM CM DM
Line OK OK OK - - OK OK -
Motor OK - - - - - - -
Control lines OK - OK - - - OK -
PROFIBUS option OK - OK - - - - -
Signal Interface<3 m OK - - - - - - -
Enclosure - - - OK OK - - OK
Load sharing OK - - - - - OK -
Standard bus OK - OK - - - OK -
Basic specificationsBasic specifications
Basic specificationsBasic specifications
Basic specifications
Line 4 kV/5kHz/DCN 2 kV/2 4 kV/12 - - 2,3 x U
N
2)
10 V
RMS
-
Motor 4 kV/5kHz/CCC - - - - - 10 V
RMS
-
Control lines 2 kV/5kHz/CCC - 2 kV/2
1)
---10 V
RMS
-
PROFIBUS option 2 kV/5kHz/CCC - 2 kV/2
1)
---10 V
RMS
-
Signal interface<3 m 1 kV/5kHz/CCC - - - - - 10 V
RMS
-
Enclosure - - -
8 kV AD
10 V/m - - -
6 kV CD
Load sharing 4 kV/5kHz/CCC - - - - - 10 V
RMS
-
Standard bus 2 kV/5kHz/CCC - 4 kV/2
1)
---10 V
RMS
-