6.7.5.
Performance Ratio
[0] [Plant]
The follower inverters in the network will use the value from the irradiation sensor connected to
the master inverter for their performance ratio calculation. When follower inverters are installed
in a different environment than the master inverter, individual irradiation sensors can be con-
nected to them to obtain a more accurate calculation of the performance ratio.
Select 'Enable' to receive notification when performance ratio falls below a limit value.
If the irradiation falls below 0.20 W/m
2
, notification of performance ratio below limit will not be
sent.
Note:
The PV array settings of the inverter must be configured before the performance ratio can
be calculated. For further details refer to [Inverter Setup Calibration].
Illustration 6.23: Performance Ratio
6.7.6.
Communication Error
[0] [Plant]
If the master inverter is unable to communicate with one or more inverters in its network, a
message will be sent to the specified recipient.
The notification is sent when communication has failed for 60 minutes or more.
Illustration 6.24: Communication Error
6.7.7.
Data Overwrite
[0] [Plant]
Check 'Enable' to activate a notification when the datalog content reaches the 60% limit of data
capacity without a log upload.
6. Setup