Illustration 6.17: Q(U) Set Point Curves - Reactive Power
Note:
A pop -up warning appears when an inconsistent pair of values is entered.
6.6.4.
Fallback Values
[1] [Plant]
When the grid management box is selected as reference value, enter fallback values. Fallback
values are automatically activated when communication fails between:
the master inverter and the grid management box
the master inverter and a follower inverter
Illustration 6.18: Fallback Values
Item
Description
Setpoint type OFF
- The fallback value is disabled. The inverters will continue to run with the
most recent configuration.
Constant reactive power Q
- The inverters will fall back to the value of reactive power Q specified in
Val-
ue
.
Constant power factor PF
- The inverters will fall back to the value of power factor PF specified in
Value
.
Value The fallback value for Q or PF.
6.7.
Messaging
[0] [Plant, Inverter]
Message types:
Yield
Event
6. Setup
42 L00410583-01_02