Step 5 of 7: Grid code
Select the grid code to match the location of the installation. To meet medium-voltage grid re-
quirements select a grid code ending in MV.
The default setting is [undefined].
Select the grid code again, to confirm.
The setting is activated immediately.
Correct selection is essential to comply with local and national standards.
Illustration 2.6: Step 5 of 7: Grid Code
Note:
If the initial and confirmation settings are different,
grid code selection is cancelled
the wizard recommences step 5
If initial and confirmation settings match, but are incorrect, contact service.
Step 6 of 7: Replication
To replicate the settings from steps 1 to 6 to other inverters in the same network
Select inverters
Click [Replicate]
Note:
When the PV configuration, installed PV power and PV array area of follower inverters in the
network differ from that of the master, do not replicate. Set up the follower inverters individ-
ually.
2. Getting Started
L00410583-01_02 11