32 User Guide DLX Series L00410623-1
4.3.6.1. Connection Procedures
Figure 4.3.30: Customer connection area with network terminals
1. CAN bus terminal
2. RS-485 terminal
3. Ethernet connector
4. Network cable gland
• Ethernet: Use CAT5e or better, with size 0.21 mm
2
/24 AWG, and a maximum total length
of 100 m.
• CAN: Use CAT5e or better, with size 0.21 mm
2
/24 AWG, with a maximum total length of
500 m.
• RS-485 Use CAT5e or better, with size 0.21 mm
2
/24 AWG, with a maximum total length
of 1200 m
• Unscrew the network cable gland, and take out the grommet.
• Three-way cable gland insert:
Figure 4.3.31: Insertion of network cables in gland
1. Conductors with connector: Cut through the grommet with a width of about 1mm.
With no connector no cutting is necessary
2. Remove the plug from inside the grommet.
3. Assemble the cable in the gap.
Repeat step 1 – 3 if more cables.
4. Guide the assembly into the cable gland.
5. Connect the cables to the terminals in the connection area as follows: