User Guide DLX Series L00410623-1 19
4.2.1. Wall Bracket
Depending on the mounting surface, different mounting methods may be required to
secure the wall bracket. The system installer is responsible for selecting the correct type
and number of fixings suitable to support the weight of the inverter on the mounting
surface.
• The bracket is designed to support 80 kg
• The inverter must be mounted in a vertical orientation!
• Mount the inverter in compliance with the minimum distances to ensure optimum
cooling. Refer to 3.2.1. Mounting. This is important with several inverters installed!
• The recommended height for the connection area is: 1000 - 1400 mm above floor level.
Figure 4.2.1: Inverter bracket
1. Carrier slots for the inverter
2. Steering slots for the inverter
3. Carrier slots for the Stringbox
4. Fixing clip
Figure 4.2.2: Distances between the fixing screws
D1. 232.5 mm
D2. 232.5 mm
D3. 75 mm
D4. 75 mm
• Mark the bracket holes on the mounting surface using a spirit level and the bracket as a
template to ensure that the bracket is correctly level.
• The mounting bracket should be fastened to the studs of a dry wall or to a
concrete/masonry wall.
• Drill the holes and fasten the bracket with the number of screws required to support the
hanging weight of the inverter.
• Fasten the inverter bracket to the wall with minimum 2 fixings.
• The installer is responsible for selecting the correct dimensions of the fixings.