8 Specifications
8.1 Electrical Data
8.1.1 Mains Supply 3x200-240 V AC
Type Designation P1K1 P1K5 P2K2 P3K0 P3K7
Typical Shaft Output [kW] 1.1 1.5 2.2 3.0 3.7
Typical Shaft Output [HP] at 208 V 1.5 2.0 2.9 4.0 4.9
IP20/Chassis
6)
A2 A2 A2 A3 A3
IP55/Type 12 A4/A5 A4/A5 A4/A5 A5 A5
IP66/NEMA 4X A4/A5 A4/A5 A4/A5 A5 A5
Output current
Continuous (3x200-240 V) [A] 6.6 7.5 10.6 12.5 16.7
Intermittent (3x200-240 V) [A] 7.3 8.3 11.7 13.8 18.4
Continuous kVA (208 V AC) [kVA] 2.38 2.70 3.82 4.50 6.00
Max. input current
Continuous (3x200-240 V) [A] 5.9 6.8 9.5 11.3 15.0
Intermittent (3x200-240 V) [A] 6.5 7.5 10.5 12.4 16.5
Additional specifications
Estimated power loss at rated max. load [W]
4)
63 82 116 155 185
IP20, IP21 max. cable cross-section (mains, motor, brake and load
sharing) [mm
2
/(AWG)]
4, 4, 4 (12, 12, 12)
(min. 0.2 (24))
IP55, IP66 max. cable cross-section (mains, motor, brake and load
sharing) [mm
2
/(AWG)]
4, 4, 4 (12, 12, 12)
Max. cable cross-section with disconnect 6, 4, 4 (10, 12, 12)
Efficiency
3)
0.96 0.96 0.96 0.96 0.96
Table 8.1 Mains Supply 3x200-240 V AC - Normal overload 110% for 1 minute, P1K1-P3K7
Specifications
VLT
®
HVAC Drive Operating Instructions
MG11AJ02 - Rev. 2013-07-31 43
8 8
Vista de pagina 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 73 74