Sleep Mode The energy-saving function is enabled. This
means that at present the motor has stopped,
but it will restart automatically when required.
Speed high Motor speed is above the value set in
4-53 Warning Speed High.
Speed low Motor speed is below the value set in
4-52 Warning Speed Low.
Standby In Auto On mode, the frequency converter will
start the motor with a start signal from a
digital input or serial communication.
Start delay
In 1-71 Start Delay, a delay starting time was
set. A start command is activated and the
motor will start after the start delay time
expires.
Start fwd/rev Start forward and start reverse were selected
as functions for 2 different digital inputs
(parameter group 5-1* Digital Inputs). The
motor will start in forward or reverse
depending on which corresponding terminal
is activated.
Stop The frequency converter has received a stop
command from the LCP, digital input or serial
communication.
Trip An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, the
frequency converter can be reset manually by
pressing [Reset] or remotely by control
terminals or serial communication.
Trip lock An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, power
must be cycled to the frequency converter.
The frequency converter can then be reset
manually by pressing [Reset] or remotely by
control terminals or serial communication.
Table 7.4 Operation Status
NOTICE
In auto/remote mode, the frequency converter
requires external commands to execute functions.
7.2 Warning and Alarm Types
Warnings
A warning is issued when an alarm condition is impending
or when an abnormal operating condition is present and
may result in the frequency converter issuing an alarm. A
warning clears by itself when the abnormal condition is
removed.
Alarms
Trip
An alarm is issued when the frequency converter is
tripped, which means that the frequency converter
suspends operation to prevent frequency converter or
system damage. The motor will coast to a stop. The
frequency converter logic will continue to operate and
monitor the frequency converter status. After the fault
condition is remedied, the frequency converter can be
reset. It will then be ready to start operation again.
Resetting the frequency converter after trip/trip lock
A trip can be reset in any of 4 ways:
Press [Reset] on the LCP
Digital reset input command
Serial communication reset input command
Auto reset
Trip lock
Input power is cycled. The motor coasts to a stop. The
frequency converter continues to monitor the frequency
converter status. Remove input power to the frequency
converter, correct the cause of the fault, and reset the
frequency converter.
Warning and Alarm Displays
A warning is displayed in the LCP along with the
warning number.
An alarm flashes along with the alarm number.
130BP086.11
Status
0.0Hz 0.000kW 0.00A
0.0Hz
0
Earth Fault [A14]
Auto Remote Trip
1(1)
Illustration 7.2 Alarm Display Example
In addition to the text and alarm code on the LCP of the
frequency converter, there are 3 status indicator lights.
Auto
on
Reset
Hand
on
Off
Back
Cancel
Info
OK
On
Alarm
Warn.
130BB467.10
Illustration 7.3 Status Indicator Lights
Diagnostics and Troubleshoo...
VLT
®
HVAC Drive Operating Instructions
34 MG11AJ02 - Rev. 2013-07-31
77