Terminal description
Terminal Parameter
Default
Setting Description
Digital Inputs/Outputs
12, 13 - +24 V DC 24 V DC supply voltage.
Maximum output
current is 200 mA total
for all 24 V loads.
Usable for digital inputs
and external
transducers.
18 5-10 [8] Start
Digital inputs.
19 5-11 [0] No
operation
32 5-14 [0] No
operation
33 5-15 [0] No
operation
27 5-12 [2] Coast
inverse
Selectable for digital
input and output.
Default setting is input.
29 5-13 [14] JOG
20 - Common for digital
inputs and 0 V
potential for 24 V
supply.
37 - Safe Torque
Off (STO)
Safe input (optional).
Used for STO.
Analog Inputs/Outputs
39 -
Common for analog
output
42 6-50 Speed 0 -
High Limit
Programmable analog
output. The analog
signal is 0-20 mA or
4-20 mA at a maximum
of 500 Ω
50 - +10 V DC 10 V DC analog supply
voltage. 15 mA
maximum commonly
used for potentiometer
or thermistor.
53 6-1 Reference Analog input.
Selectable for voltage
or current. Switches
A53 and A54 select mA
or V.
54 6-2 Feedback
55 -
Common for analog
input
Serial Communication
61 -
Integrated RC-Filter for
cable screen. ONLY for
connecting the screen
when experiencing EMC
problems.
68 (+) 8-3
RS-485 Interface. A
control card switch is
provided for
termination resistance.
69 (-) 8-3
Relays
01, 02, 03 5-40 [0] [0] Alarm
Form C relay output.
Usable for AC or DC
voltage and resistive or
inductive loads.
04, 05, 06 5-40 [1] [0] Running
Table 4.3 Terminal Description
Additional terminals:
•
2 form C relay outputs. Location of the outputs
depends on frequency converter configuration.
•
Terminals located on built-in optional equipment.
See the manual provided with the equipment
option.
4.8.2
Wiring to Control Terminals
Control terminal connectors can be unplugged from the
frequency converter for ease of installation, as shown in
Illustration 4.10.
NOTICE
Keep control wires as short as possible and separate
from high power cables to minimise interference.
1. Open the contact by inserting a small screw
driver into the slot above the contact and push
the screw driver slightly upwards.
130BD546.10
2
1
10 mm
29
27
32
19
18
13
12
33
Illustration 4.12 Connecting Control Wires
Electrical Installation
VLT
®
HVAC Drive Operating Instructions
MG11AJ02 - Rev. 2013-07-31 17
4 4
Comentarios a estos manuales