4.8.6 RS-485 Serial Communication
Up to 32 nodes can be connected as a bus, or via drop
cables from a common trunk line to 1 network segment.
Repeaters can divide network segments. Each repeater
functions as a node within the segment in which it is
installed. Each node connected within a given network
must have a unique node address, across all segments.
Connect RS-485 serial communication wiring to
terminals (+)68 and (-)69.
Terminate each segment at both ends, using
either the termination switch (bus term on/off,
see Illustration 4.13) on the frequency converters,
or a biased termination resistor network.
Connect a large surface of the screen to ground,
for example with a cable clamp or a conductive
cable gland.
Apply potential-equalising cables to maintain the
same ground potential throughout the network.
Use the same type of cable throughout the entire
network to prevent impedance mismatch.
Cable
Screened twisted pair (STP)
Impedance
120 Ω
Max. cable
length [m]
1200 (including drop lines)
500 station-to-station
Table 4.4 Cable Information
Electrical Installation
VLT
®
HVAC Drive Operating Instructions
MG11AJ02 - Rev. 2013-07-31 19
4 4