41
MG.60.N2.02 - VLT is a registered Danfoss trademark
VLT
®
5000 / VLT
®
6000 HVAC / VLT
®
8000 AQUA
Data Value:
Preprogrammed (FACTORY SETUP) [0]
Setup 1 (SETUP 1) [1]
Setup 2 (SETUP 2) [2]
Setup 3 (SETUP 3) [3]
Setup 4 (SETUP 4) [4]
★ Active Setup (ACTIVE SETUP) [5]
★ Factory Setting
805
Control Word
Bit 10 Function
Selection:
No function
(NO FUNCTION) [0]
★ Bit 10 = 1: control word active
(BIT 10 = 1 >CTW ACTIVE) [1]
Bit 10 = 0: control word active
(BIT 10 = 0 >CTW ACTIVE) [2]
Bit 10 = 0: bus time out
(BIT 10 = 0 >TIME OUT) [3]
Function:
According to the drive's standard
communications profile, control word and
speed reference will be ignored if bit 10 of the
control word is
0
. Parameter 805 lets the user
change the function of bit 10. This is some
times necessary, as some masters set all bits
to
0
in various fault situations. In these cases,
it makes sense to change the function of bit
10 so that the VLT is commanded to stop
(coast) when all bits are
0
.
Description of Selections:
•
No function
. Bit 10 is ignored, i.e.,
control word and speed reference are
always valid.
•
Bit 10
=
1
>CTW active
. The control
word and speed reference are
ignored if bit 10 = 0.
•
Bit 10
=
0
>CTW active
. The control
word and speed reference are
ignored if bit 10 = 1. If all bits of the
control word are 0, the VLT reaction
will be coasting.
•
Bit 10
=
0
>time out
. The time out
function selected in parameter 804 is
activated when bit 10 is
0
.
Data Value:
Disable (DISABLE) [0]
★ Enable (ENABLE) [1]
This parameter determines LonWorks control
of the drive. When
Enable
is selected, drive
parameters 503 through 508 determine the
interaction between various LonWorks and
digital drive input commands. See the
VLT Instruction Manual
for details.
When this parameter is set to
Store active
setup
, LonWorks downloaded parameters are
written to EEPROM and stored.
Store edit
setup
stores the setup selected in parameter
970.
Store all setups
stores all setups in
parameter 970. When finished (appx. 15 sec.),
it automatically returns to
No action
. Any
parameters values written via the serial bus
with
No action
selected are lost when power
is removed from the drive. The function is only
activated with the VLT in stop mode.
Data Value:
Disable (DISABLE) [0]
★ Enable (ENABLE) [1]
This parameter determines if LonWorks can
be used to access and edit drive parameters.
927
Parameter edit
928
Process control
970
Edit setup select
971
Store data value
Data Value:
★ No action (NO ACTION) [0]
Store all setups
(STORE ALL SETUPS [1]
Store edit setup
(STORE EDIT SETUP) [2]
Store active setup
(STORE ACTIVE SETUP) [3]
With
Bit 10
=
0
>CTW active
selected
,
nviStartStop and
nviResetFault commands will not
function.
CAUTION
!
This parameter selects the setup being edited,
through either the drive control panel or
LonWorks. The drive may operate in one
setup while editing another.
Active setup
selects the parameter being edited as the
setup controling drive operation.