TripleLynx CN inverter type No. of PV
inputs
Overall DC limit for
the inverter
Default DC power
limit per PV input
DC power limit per
PV input
TripleLynx CN 8 kW 2 8.2 kW 5.15 kW 6.0 kW
TripleLynx CN 10 kW 2 10.3 kW 5.15 kW 6.0 kW
TripleLynx CN 12.5 kW 3 12.9 kW 5.15 kW 6.0 kW
TripleLynx CN 15 kW 3 15.5 kW 5.15 kW 6.0 kW
Table 3.3: DC Power Limits
PV Power Settings for Asymmetrical PV Configuration
When the levels of the connected PV power differ from one input to the next, the PV configura-
tion is defined as asymmetric.
For asymmetric PV configuration, choose installed PV power settings optimally, to utilise the po-
tential of 6 kW per input to increase performance and avoid unintentional loss.
The installed PV power is defined as the generated PV-to-Grid power. To calculate these values
use the module standard test condition (STC) values [kWp] and divide by the PV-to-Grid ratio
(Kpv-ac).
Determination of PV Input Settings
Allocate values for each PV input, ensuring that:
• The amount of installed PV power is correct.
• The ‘overall DC limit for the inverter’ is not exceeded.
• Each value does not exceed the maximum 6 kW DC power per PV input.
Configure PV Inputs
To enter the PV power settings for an asymmetric layout, access at security level 1 is required.
•
In the display, go to [Setup → Setup details → PV configuration].
In the Web Server, go to [Inverter→ Setup → Setup details → PV configuration].
• De-select Auto detect
• Select Individual or Parallel.
• Enter PV input values.
• Enter PV array areas (optional).
3.3.5. MPPT
A Maximum Power Point Tracker (MPPT) is an algorithm which is constantly trying to maximise
the output from the PV array. The MPPT included in the TripleLynx CN range of inverters is
based on the Incremental-Conductance algorithm. The algorithm updates the PV voltage fast
enough to follow quick changes in solar irradiance, 30 W/(m
2
*s).
3. Description of the Inverter
L00410582-01_02 19
3