VL 8000 AQUA
Installation
High voltage test
A high voltage test can be carried out by short-circuiting
terminalsU,V,W,L
1
,L
2
and L
3
and energizing
by max. 2.5 kV DC for one second between
this short-circuit and the chassis.
NOTE
The RFI switch must be closed (position ON)
when high voltage tests are carried out . The
line and motor connection must be interrupted
in the case of high voltage tests of the total installation
if the leakage currents are too high.
Heat emission from VLT 8000 AQUA
ThetablesinGeneral technical data show the
power loss P
ϕ
(W) from VLT 8000 AQUA. The
maximum cooling air temperature t
IN, MAX
is 40° C
(104° F) at 100% load (of rated value).
Ventilation of integrated VLT 8000 AQUA
The quantity of air required for cooling AFD
can be calculated as follows:
1. Add up the values of P for all the AFDs to be
integrated in the same panel.
The highest cooling air temperature (t
IN
) present
must be lower than t
IN, MAX
40° C (104° F).
The day/night average must be 5°C (9° F) lower.
The outlet temperature of the cooling air must
not exceed: t
OUT, MAX
45° C (113° F).
2. Calculate the permissible difference between
the temperature of the cooling air (t
IN
)and
its outlet temperature (t
OUT
):
t= 45° C (113° F) -t
IN
.
3. Calculate the required
Insert t in Kelvin
The outlet from the ventilation must be placed
above the highest-mounted AFD.
Allowance must be made for the pressure loss
across the filters and for the fact that the pressure
is going to drop as the filters are choked.
MG.80.A6.22 - VLT is a registered Danfoss trademark
55