VL 8000 AQUA
Installation
RFI switch
M
ains supply isolated from earth:
If the adjustable frequency drive is supplied from an
isolated mains source (IT mains and grounded delta),
the RFI switch can be turned off (OFF). In OFF position,
the internal RFI capacities (filter capacitors) between
the chassis and the intermediate circuit are cut off to
avoid damage to the intermediate circuit and to reduce
the earth capacity currents (according to IEC 61800-3).
NOTE
TheRFIswitchisnottobeoperatedwith
mains connected to the unit. Check that
the mains supply has been disconnected
before operating the RFI switch.
NOTE
Open RFI switch is only allowed at factory
set switching frequencies.
NOTE
The RFI switch disconnects the capacitors
galvanically to ground.
The red switches are operated by means of e.g. a
screwdriver. They are set in the OFF position when
they are pulled out and in ON position when they are
pushed in (see drawing below). Factory setting is ON.
Mains supply connected to earth:
The RFI switch must be in ON position in order
for the adjustable frequency drive to comply
with the EMC-standard.
Compact IP 20/NEMA 1
VLT 8006 - 8011 380 - 480 V
VLT 8002 - 8011 525 - 600 V
Compact IP 20/NEMA 1
VLT 8016 - 8027 380 - 480 V
VLT 8006 - 8011 200 - 240 V
VLT 8016 - 8027 525 - 600 V
Compact IP 20/NEMA 1
VLT 8032 - 8042 380 - 480 V
VLT 8016 - 8022 200 - 240 V
MG.80.A6.22 - VLT is a registered Danfoss trademark
53