VLT® 8000 AQUAInstallation Mechanical installationPlease pay attention to the requirementsthat apply to integration and field mountingkit, see the be
VLT® 8000 AQUA EMC-correct electrical installation525-600 V units do not comply with EuropeanEMC and Low Voltage Directives.The following is a guidel
VLT® 8000 AQUAInstallationMG.80.A6.22 - VLT is a registered Danfoss trademark57
VLT® 8000 AQUAMG.80.A6.22 - VLT is a registered Danfoss trademark58
VLT® 8000 AQUAInstallation Earthing/Grounding of shielded/armoredcontrol cablesGenerally speaking, control cables must be shielded/armored and the sh
VLT® 8000 AQUA Electrical installation, enclosuresCompact IP 54/NEMA 12VLT 8006-8011, 380-480 VCompact IP 20/NEMA 1VLT 8006-8011, 380-480 VVLT 8002-8
VLT® 8000 AQUAInstallationCompact IP 54/NEMA 12VLT 8006-8032, 200-240 VVLT 8016-8072, 380-480 VCompact IP 20/NEMA 1VLT 8042-8062, 200-240 VVLT 8100-81
VLT® 8000 AQUACompact IP 20/NEMA 1VLT 8102-8122, 380-480 VCompact IP 54/NEMA 12VLT 8102-8122, 380-480 VIP 00/ChassisVLT 8200-8300, 525-600 VCompact IP
VLT® 8000 AQUAInstallationIP 54/NEMA 12, IP 21/NEMA 1VLT 8152-8352, 380-480 VIP 00/ChassisVLT 8152-8352, 380-480 VIP 54/NEMA 12, IP 21/NEMA 1 with dis
VLT® 8000 AQUACompact IP 00/Chassis, IP 20/NEMA 1,and IP 54/NEMA 12VLT 8450-8600, 380-480 VMG.80.A6.22 - VLT is a registered Danfoss trademark64
VLT® 8000 AQUAInstallation Electrical installation, power cablesIP 20/NEMA 1VLT 8006-8032, 200-240 VVLT 8016-8122, 380-480 VVLT 8016-8072, 525-600 VC
VLT® 8000 AQUASide by side/flange by flangeAll AFDs can be mounted side by side/flange by flange.d[mm/in] CommentsCompact (all enclosure types)VLT 800
VLT® 8000 AQUA Electrical installation, power cablesIP 00/Chassis and IP 20/NEMA 1VLT 8042-8062, 200-240 VVLT 8100-8150, 525-600 VIP 00/Chassis and I
VLT® 8000 AQUAInstallation Electrical installation, power cablesCompact IP 00/Chassis, IP 20/NEMA 1, and IP 54/NEMA 12VLT 8450-8600 380-480 V without
VLT® 8000 AQUA Use of EMC-correct cablesBraided shielded/armored cables are recommendedto optimise EMC immunity of the control cables andthe EMC emis
VLT® 8000 AQUAInstallation Tightening torque and screw sizesThe table shows the torque required when fittingterminals to the AFD. For VLT 8006-8032,
VLT® 8000 AQUA Line connectionLine must be connected to terminals 91, 92, 93.Nos. 91, 92, 93 Line voltage 3 x 200-240 VL1, L2, L3 Line voltage 3 x 38
VLT® 8000 AQUAInstallationThe total current consumption of the motorsis not to exceed the maximum rated outputcurrent IVLT,Nfor the AFD.Problems may a
VLT® 8000 AQUA Motor thermal protectionThe electronic thermal relay in UL-approved AFD hasreceived UL-approval for single motor protection, aslong as
VLT® 8000 AQUAInstallation Control cardAll terminals for the control cables are locatedunder the protective cover of the AFD.The protective cover (se
VLT® 8000 AQUA61 Termination of serial communication.See Earthing/Grounding of shielded(armoured control cables.This terminal is not normally to beuse
VLT® 8000 AQUAInstallation Bus connectionThe serial bus connection in accordance with the RS485 (2-conductor) norm is connected to terminals68/69 of
VLT® 8000 AQUAInstallation Installation of VLT 8450-8600 380-480 V Compact IP00/Chassis, IP 20/NEMA 1 and IP 54/NEMA 12Cooling Side-by-sideAll units
VLT® 8000 AQUA Connection example VLT 8000 AQUAThe diagram below gives an example of a typicalVLT 8000 AQUA installation.The line supply is connected
VLT® 8000 AQUAInstallation Connection examples Single-pole start/stop- Start/stop using terminal 18.Parameter 302 = Start [1]- Quick-stop using term
VLT® 8000 AQUA 3-wire start/stop- Stop inverse by means of terminal 32.Parameter 306 = Stop inverse[14]- Latched start using terminal 18.Parameter 30
VLT® 8000 AQUAInstallation Control unit LCPThe front of the AFD features a control panel - LCP(Local Control Panel). This is a complete interface for
VLT® 8000 AQUA[QUICK MENU] gives access to theparameters used for the Quick menu.It is possible to switch between theQuick menu and the Extend menumod
VLT® 8000 AQUAInstallationNOTEAn active HAND-OFF-AUTO signal via the digitalinputs will have higher priority than the controlkeys [HAND START]-[AUTO S
VLT® 8000 AQUA Display mode II:This display mode makes it possible to have threeoperating data values displayed at the same timein line 1. The operat
VLT® 8000 AQUAInstallation Navigation between display modes175ZA697.10HAND LOCAL RUNNING0 ---- 60Display mode I40.0HzAUTO REMOTE RUNN
VLT® 8000 AQUA Changing dataRegardless of whether a parameter has beenselected under the Quick menu or the Extendedmenu, the procedure for changing d
VLT® 8000 AQUAInstallation Infinitely variable change of numeric data valueIf the chosen parameter represents a numeric datavalue, a digit is first s
VLT® 8000 AQUA General information about electrical installation High voltage warningThe voltage of the AFD is dangerouswhenever the equipment is co
VLT® 8000 AQUA Quick MenuThe QUICK MENU key gives access to 12 of themost important setup parameters of the drive. Afterprogramming, the drive will,
VLT® 8000 AQUAInstallationNOTEProgramming of extended parameters functionsavailable through EXTENDED MENU key isdone in accordance with same procedure
VLT® 8000 AQUAInstallationor iron. Shield armor intended for mechanicalprotection, for example, is not suitable.MG.80.A6.22 - VLT is a registered Danf
VLT® 8000 AQUA Extra protection with regard to indirect contactELCB relays, multiple protective grounding orgrounding can be used as extra protection
VLT® 8000 AQUAInstallation RFI switchMains supply isolated from earth:If the adjustable frequency drive is supplied from anisolated mains source (IT
VLT® 8000 AQUAVLT 8032 - 8042 525 - 600 VCompact IP 20/NEMA 1VLT 8052 - 8122 380 - 480 VVLT 8027 - 8032 200 - 240 VVLT 8052 - 8072 525 - 600 VCompact
VLT® 8000 AQUAInstallation High voltage testA high voltage test can be carried out by short-circuitingterminalsU,V,W,L1,L2and L3and energizingby max.