VL 8000 AQUA
Installation
Connection examples
Single-pole start/stop
- Start/stop using terminal 18.
Parameter 302 = Start [1]
- Quick-stop using terminal 27.
Parameter 304 = Coasting stop, inverse [0]
Digital speed up/down
- Speed up and down using terminals 32 and 33.
Parameter 306 = Speed up [7]
Parameter 307 = Speed down [7]
Parameter 305 = Freeze reference [2]
Potentiometer reference
-Parameter 308 = Reference [1]
Parameter 309 = Terminal 53, min. scaling
Parameter 310 = Terminal 53, max. scaling
Run permissive
- Start permitted with terminal 16.
Parameter 300 = Run permissive [8].
- Start/stop with terminal 18.
Parameter 302 = Start [1].
- Quickstop with terminal 27.
Parameter 304 = Coasting stop, inverse [0].
- Activated peripheral equip
Parameter 323 = Start command active [13].
2-zone regulation
- Parameter 308 = Feedback [2].
- Parameter 311 = Feedback [2].
Transmitter connection
- Parameter 314 = Reference [1]
- Parameter 315 = Terminal 60, min. scaling
- Parameter 316 = Terminal 60, max. scaling