Danfoss REP24CO3 Especificaciones Pagina 78

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 84
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 77
78
The REP range offers 0-10v output
proportional control designed for use
controlling fan coil or chilled ceiling
units or any other system that requires
0-10v proportional control. Available
with various options for manual or auto
fan speed control as well as options for
using motorised or wax filled actuators,
these thermostats provide a solution
for most heat/cool manual changeover
requirements.
The slower response of wax filled
actuators compared to the relative
speed of motorised actuators means
that different control algorithms are
needed within a thermostat to ensure
accurate temperature control. A simple
DIL switch selection for motorised
or wax at time of installation ensures
accurate and stable control for the
minimum of fuss.
On all models, range and limit locking
are available allowing the installer to
limit or lock the temperature range
of the thermostat (e.g. 18-22ºC),
ideal in public buildings or office
environments.
Frost protection mode is available in
heating mode. If the dial is turned
down below the 10ºC mark on the dial,
frost protection is activated (indicated
by the right LED turning orange)
meaning that if the temperature drops
below 8ºC the output will engage.
Frost protection is not available in
cooling mode, however, if the dial is
turned below 10ºC in cooling mode
the unit enters standby mode and the
unit is inactive until the dial is turned
above 10ºC again.
Overall the REP range provides a versatile
and efficient solution for almost all
installations requiring 24v input 0-10v
output manual heat/cool changeover
with or without fan control.
REP24 REP24 CO
Application Example
+
-
REP24 REP24CO REP24CO1 REP24CO3
Code No. 087N775000 087N775200 087N775400 087N775600
Temperature Range 10-30°C
Power Output 0-10 Vdc
Power Supply 24 Vac/Vdc +/- 15%
Switching Differential <1°C
Control Method
P + I
Proportional Band 2°K
Internal Heat/Cool Selection
Front mounted Heat/Cool
Switch
Fan Speeds 0 0 1 3
Manual fan speed selector N/A N/A No Yes
Auto/Manual Fan N/A N/A
Frost Protection
Standby (Cooling)
Motorised or Wax
Actuator Selection
Power LED Yes Yes Yes Yes
Output LED Yes Yes Yes Yes
Ambient Operating
Temperature
-10 to +45°C
Dimensions (mm)
85 w x 86 h x 42 d 110w x 90 h x 40 d 110 w x 90 h x 40 d 110 w x 90 h x 40 d
Heat/Cool Thermostats
0-10v Proportional Control
Vista de pagina 77
1 2 ... 73 74 75 76 77 78 79 80 81 82 83 84

Comentarios a estos manuales