Installed together with ASV-PV to •
control the differential pressure in
risers
Shut-off valve•
Easy to install - all service parts •
located at 90º angle to valve
Connection for impulse tube to •
ASV-PV
Can be fitted with measuring •
nipples
The ASV-M is a manual shut-off valve
designed to be used in combination
with the pressure controller ASV-PV.
The ASV-M is not supplied as standard
with nipples for measuring, but can be
equipped with them if required.
Type DN
Kvs
m
3
/h
Internal Thread
ISO 7/1
Code No. Type
External Thread
ISO 228/1
Code No.
15 1.6 Rp ½ 003L769100 G ¾ A 003L769600
20 2.5 Rp ¾ 003L769200 G 1 A 003L769700
25 4.0 Rp 1 003L769300 G 1¼ A 003L769800
32 6.3 Rp 1¼ 003L769400 G 1½ A 003L769900
40 10 Rp 1½ 003L769500 G 1¾ A 003L770000
50 16 G 2¼ A 003L770200
ASV in manifold
for floor heating system
ASV with
fan coil
ASV-PVandASV-M
ASV-MDN50
Flow Return
Shut-Off Valve
ASV-M
Description Comments Code No.
Differential pressure measuring connector
For drain cock 003L814300
Drain Cock
For ASV-PV (DN 15-50) 003L814100
Two measuring nipples and one locking plate
For AAV-I and ASV-M,
rectus type
003L814500
Impulse tube, with O-rings 1.5m 003L815200
2.5m 003Z069000
5.0m 003L815300
Adapter large ASV
1)
G ¼ - R ¼; G
1
/
16
003Z069100
Nipple for connecting impulse tube
2)
G
1
/
16
- R ¼ 003L815100
O-ring for impulse tube
3)
2.90 x 1.78 003L817500
Plug for impulse tube connection ASV-I/M 3) G
1
/
16
A 003L817400
1) Recommended for use with MSV-F2, connected to measuring hole, it allows connection of impulse tube from
ASV while retaining measuring functionality.
2) Recommended for use with MSV-F2, connected to measuring hole. Can also be used for connecting impulse
tube directly on the pipe.
3) Set of 10 pieces
ASV-M