2. Connect terminals 14 and 16 to an
ohmmeter .
3. Turn screw until the cam switches
the end switch and the ohmmeter
shows 0 Ω.
The end switches are adjusted.
Dismounting of Valve and
Actuator
11
DANGER!
Danger of injury by steam or hot water!
Valve without actuator is open , sealing
is in the actuator.
It is absolutely necessary to depressurize
system prior to dismounting.
Carry out dismounting in reverse order as
mounting.
Installation Guide AMV 410, AMV 413
DEN-SMT/SI VI.AA.U4.7S Danfoss Heating