Danfoss VLT 2800 Manual de servicio Pagina 68

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 95
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 67
VLT
®
2800 Series
Connection examples
Start/stop
Start/stop using terminal 18 and coasting
stop using terminal 27.
Par. 302 Digital input = Start [7]
Par. 304 Digital input = Co asting stop inverted [2]
For Precise start/stop the following settings are made:
Par. 302 Digital input = Precise start/stop [27]
Par. 304 Digital input = Co asting stop inverted [2]
Pulse start/stop
Pulse start using terminal 18 and pulse stop
using terminal 19. In addition, the jog frequency
is activated via terminal 29.
Par. 302 Digital input = Pulse start [8]
Par. 303 Digital input = Stop inverted [6]
Par. 304 Digital input = Co asting stop inverted [2]
Par. 305 Digital input = Jog [13]
Speed up/down
Speed up/down using terminals 29/33.
Par. 302 Digital input = Start [7]
Par. 303 Digital input = Freeze reference [14]
Par. 305 Digital input = Speed up [16]
Par. 307 Digital input = Speed down [17]
Potentiometer reference
Voltage reference via a potentiometer.
Par. 308 Analog input = Reference [1]
Par. 309 Terminal 53, min. scaling =0Volt
Par. 310 Terminal 53, max. scaling =10Volt
Connection of a 2-wire transmitter
Connection of a 2-wire transmitter as feedback
to terminal 60.
Par. 314 Analog input = Feedback [2]
Par. 315 Terminal 60, min. scaling =4mA
Par. 316 Terminal 6 0, max. scaling =20mA
MG.28.A9.02 - VLT is a registered Danfoss trademark