Danfoss VLT 2800 Manual de servicio Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 95
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
VLT
®
2800 Series
Description of choice:
Factory S etup [0] contains the factory-set parameter
values. Setup 1-4 [1]-[4] are four individual
Setups which can be selected as required. Multi
Setup [5] is used where remote-controlled shifts
between the four Setups via a digital input or via
serial communication is required.
005 Programming Setup
(EDIT SETUP)
Value:
Factory Setup (FACTORY SETUP)
[0]
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
Setup 3 (SETUP 3)
[3]
Setup 4 (SETUP 4)
[4]
Active Setup (ACTIVE SETUP)
[5]
Function:
You can select which Setup you want to programme
during operation (applies both via the control
panel and the serial communication port). It is,
for example, possible to programme Setup 2
[2], while the active Setup is set to Setup 1 [1]
in parameter 004 Active Setup .
Description of choice:
Factory Setup [0] contains the factory-set data
and can be used as a source of data if the
other Setups are to be reset to a known status.
Setup 1-4 [1]-[4] are individual Setups that can
be programmed freely during operation. If Active
Setup [5] is selected, the programming Setup will
be equal to parameter 004 Act ive Setup.
NB!:
If data is modified or copied to the active
Setup, the modifications have an immediate
effect on the unitsoperation.
006 Setup copying
(SETUP COPY)
Value:
No copying (NO COPY)
[0]
Copy to Setup 1 from #
(COPY TO SETUP 1)
[1]
Copy to Setup 2 from #
(COPY TO SETUP 2)
[2]
Copy to Setup 3 from #
(COPY TO SETUP 3)
[3]
Copy to Setup 4 from #
(COPY TO SETUP 4)
[4]
Copy to all Setups from # (COPY TO ALL)
[5]
Function:
You can copy from the selected active Setup in
parameter 005 Programming setup to the selected
Setup or Setups in this parameter.
NB!:
Copying is only possible in Stop (motor stopped
in connection with a stop command).
Description of choice:
Copying begins when the required copying function
has been selected and the [OK]/[CHANGE DATA]
key has been pushed. The display indicates
when copying is in progress.
007 LCP copy
(LCP COPY)
Value:
No copying (NO COPY)
[0]
Upload all parameters (UPL. ALL PAR.)
[1]
Download all parameters (DWNL. ALL PAR.)
[2]
Download size-independent parameters
(DWNL.OUTPIND.PAR.)
[3]
Function:
Parameter 007 LCP copy is used if you want to use
the LCP 2 control panels integral copy function. The
function is used if you want to copy all parameter
setups from one frequency converter to another
by moving the LCP 2 control panel.
Description of choice:
Select Upload all parameters [1] if you want all
parameter values to be transferred to the control
panel. Select Download all parameters [2] if all
parameter values transferred are to be copied to the
frequency converter to which the control panel is
attached. Select Download size-independent par. [3]
if you only want to downloade the size-independent
parameters. This is used when downloading to a
frequency converter with a different rated power size
than that from which the parameter setup originates.
NB!:
Upload/download can only be performed
in stop mode. Download can o
nly be
performed to a frequency converter with
the same software version number, see parameter
626 Database identification no.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A9.02 - VLT is a registered Danfoss trademark
12
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 94 95

Comentarios a estos manuales