DKSI.PK.02.A3.02 Produced by Danfoss A/S ©

Ulsnaes 1
DK-6300 Graasten
Denmark
Tel: +45 7488 1300
Fax: +45 7488 1301
E-mail: solar-inverters@danfoss.com

   
Specication:
Nominal power DC 8250 W 10300 W 12900 W 15500 W
Max recommended PV
power at STC
1)
9500 Wp 11800 Wp 14700 Wp 17700 Wp
Nominal power AC 8000 W 10000 W 12500 W 15000 W
Max power AC 8000 W 10000 W 12500 W 15000 W
Max eciency 97.9 % 98 % 98 % 98 %
Euro eciency 97 % 97 % 97.3 % 97.4 %
Night consumption < 5 W < 5 W < 5 W < 5 W

Max voltage DC 1000 V 1000 V 1000 V 1000 V
Nominal voltage DC 700 V 700 V 700 V 700 V
MPP voltage range – nominal
power
2)
345-800 V 430-800 V 358-800 V 430-800 V
AC Voltage range 3x230 V ± 20 % 3x230 V ± 20 % 3x230 V ± 20 % 3x230 V ± 20 %
Grid frequency 50 ± 5 Hz 50 ± 5 Hz 50 ± 5 Hz 50 ± 5 Hz

Max current DC 2 x 12 (24) A 2 x 12 (24) A 3 x 12 (36) A 3 x 12 (36) A
Nominal current AC 3 x 12 A 3 x 15 A 3 x 19 A 3 x 22 A
Max current AC 3 x 13.2 A 3 x 15 A 3 x 19 A 3 x 22 A
Distortion (THD %) < 4% < 5% < 5% < 5%

Dimensions (L,W,H) 700x525x250 mm 700x525x250 mm 700x525x250 mm 700x525x250 mm
Weight 35 kg 35 kg 35 kg 35 kg
Acoustic Noise level 56 dB(A) 56 dB(A) 56 dB(A) 56 dB(A)
Operation temperature
range
-25..6C (>4C derating) -25..60°C (>45°C derating) -25..60°C (>45°C derating) -25..60°C (>45°C derating)
MPPT eciency (static) 99.9 % 99.9 % 99.9 % 99.9 %
MPPT eciency (dynamic) 99.8 % 99.8 % 99.8 % 99.8 %
Overload operation Change of operating point Change of operating point Change of operating point Change of operating point
Grid surveillance Three phase monitoring Three phase monitoring Three phase monitoring Three phase monitoring
IP IP 54 IP 54 IP 54 IP 54
Isolation monitoring Value country dependent Value country dependent Value country dependent Value country dependent

Master inverter Yes Yes Yes Yes
Monitoring Web server Web server Web server Web server
Grid management PLA PLA PLA PLA
Communication Ethernet Ethernet Ethernet Ethernet
RS485 RS485 RS485 RS485
Potential free contact x 1 x 1 x 1 x 1
Sensor input x 2 (temperature, irradiation) x 2 (temperature, irradiation) x 2 (temperature, irradiation) x 2 (temperature, irradiation)
Energy meter S0 input S0 input S0 input S0 input
Options:
Modem GSM GSM GSM GSM
Grid Management Reactive power Reactive power Reactive power
1)
For xed systems with semi optimal conditions.
2)
At identical input voltages. At unequal input voltages V
mpp min
lies between 250-430 V depending on total input power.