NB!
Must be set to [5]
Stop and trip
for operation with the Interbus option.
[7] Select set-up 1 This option changes the set-up upon reestablishment of communication following a control word
time-out. If communication resumes causing the time-out situation to disappear, par. 8-05
End-of-
time-out Function
defines whether to resume the set-up used before the time-out or to retain the
set-up endorsed by the time-out function. Note the following configuration required in order to
change the set-up after a time-out: Set Par. 0-10
Active set-up to Multi set-up
[9], and select the
relevant link in par. 0-12
This Set-up Linked To
.
[8] Select set-up 2 This option changes the set-up upon reestablishment of communication following a control word
time-out. If communication resumes causing the time-out situation to disappear, par. 8-05
End-of-
time-out Function
defines whether to resume the set-up used before the time-out or to retain the
set-up endorsed by the time-out function. Note the following configuration required in order to
change the set-up after a time-out: Set Par. 0-10
Active set-up to Multi set-up
[9], and select the
relevant link in par. 0-12
This Set-up Linked To
.
[9] Select set-up 3 This option changes the set-up upon reestablishment of communication following a control word
time-out. If communication resumes causing the time-out situation to disappear, par. 8-05
End-of-
time-out Function
defines whether to resume the set-up used before the time-out or to retain the
set-up endorsed by the time-out function. Note the following configuration required in order to
change the set-up after a time-out: Set Par. 0-10
Active set-up to Multi set-up
[9], and select the
relevant link in par. 0-12
This Set-up Linked To
.
[10] Select set-up 4 This option changes the set-up upon reestablishment of communication following a control word
time-out. If communication resumes causing the time-out situation to disappear, par. 8-05
End-of-
time-out Function
defines whether to resume the set-up used before the time-out or to retain the
set-up endorsed by the time-out function. Note the following configuration required in order to
change the set-up after a time-out: Set Par. 0-10
Active set-up to Multi set-up
[9], and select the
relevant link in par. 0-12
This Set-up Linked To
.
8-05 End-of-Timeout Function
Option: Function:
Select the action after receiving a valid control word following a time-out. This parameter is active
only when par. 8-04 Control
Timeout Function
is set to [Set-up 1-4].
[0] Hold set-up Retains the set-up selected in par. 8-04 Control
Timeout Function
and displays a warning, until par.
8-06 Reset
Control Timeout
toggles. Then the frequency converter resumes its original set-up.
[1] * Resume set-up Resumes the set-up active prior to the time-out.
8-06 Reset Control Word Timeout
This parameter is active only when
Hold set-up
[0] has been selected in par. 8-05
End-of-Timeout Function
.
Option: Function:
[0] * Do not reset Retains the set-up specified in par. 8-04 Control
Word Timeout Function
, following a control word
time-out.
[1] Do reset Returns the frequency converter to the original set-up following a control word time-out. The fre-
quency converter performs the reset and then immediately reverts to the
Do not reset
[0] setting
8-07 Diagnosis Trigger
Option: Function:
This parameter has no function for LonWorks.
[0] * Disable
[1] Trigger on alarms
[2] Trigger alarm/warn.
7. Parameters FC 300 Interbus Operating Instructions
34
MG.33.H3.02 - VLT is a registered Danfoss trademark