5.1.10 13-** Smart Logic
Par.
No. #
Parameter description Default value 2-set-up Change
during
operation
Conver-
sion index
Type
13-0* SLC Settings
13-00 SL Controller Mode [0] Off 1 set-up TRUE - Uint8
13-01 Start Event [39] Start command 1 set-up TRUE - Uint8
13-02 Stop Event [40] Drive stopped 1 set-up TRUE - Uint8
13-03 Reset SLC [0] Do not reset SLC 1 set-up TRUE - Uint8
13-1* Comparators
13-10 Comparator Operand [0] Disabled 1 set-up TRUE - Uint8
13-11 Comparator Operator [1] Approx.Equal (~) 1 set-up TRUE - Uint8
13-12 Comparator Value 0.0 N/A 1 set-up TRUE -1 Int32
13-2* Timers
13-20 SL Controller Timer 0.0 s 1 set-up TRUE -2 uint_32
13-4* Logic Rules
13-40 Logic Rule Boolean 1 [0] False 1 set-up TRUE - Uint8
13-41 Logic Rule Operator 1 [0] Disabled 1 set-up TRUE - Uint8
13-42 Logic Rule Boolean 2 [0] False 1 set-up TRUE - Uint8
13-43 Logic Rule Operator 2 [0] Disabled 1 set-up TRUE - Uint8
13-44 Logic Rule Boolean 3 [0] False 1 set-up TRUE - Uint8
13-5* States
13-51 SL Controller Event [0] False 1 set-up TRUE - Uint8
13-52 SL Controller Action [0] Disabled 1 set-up TRUE - Uint8
5.1.11 14-** Special Functions
Par.
No. #
Parameter description Default value 2-set-up Change
during
operation
Conver-
sion index
Type
14-0* Inverter Switching
14-01 Switching Frequency ExpressionLimit All set-ups TRUE - Uint8
14-03 Overmodulation [1] On All set-ups FALSE - Uint8
14-08 Damping Gain Factor 96.0 % All set-ups TRUE 0 uint_8
14-1* Mains On/Off
14-12 Function at Mains Imbalance [0] Trip 1 set-up TRUE - Uint8
14-2* Reset Functions
14-20 Reset Mode [0] Manual reset All set-ups TRUE - Uint8
14-21 Automatic Restart Time 10.0 s All set-ups TRUE 0 uint_16
14-22 Operation Mode [0] Normal operation All set-ups TRUE - Uint8
14-27 Action At Inverter Fault [1] Warning All set-ups TRUE - Uint8
14-4* Energy Optimising
14-40 VT Level 90 % All set-ups FALSE 0 uint_8
14-41 AEO Minimum Magnetisation 66 % All set-ups FALSE 0 uint_8
14-5* Environment
14-50 RFI Filter [1] On 1 set-up FALSE - Uint8
14-51 DC-Link Voltage Compensation [1] On All set-ups FALSE - Uint8
14-52 Fan Control [0] Auto 1 set-up TRUE - Uint8
14-53 Fan Monitor [1] Warning 1 set-up TRUE - Uint8
14-55 Output Filter [0] No Filter 1 set-up FALSE - Uint8
14-6* Auto Derate
14-63 Min Switch Frequency 1.0 kHz 1 set-up FALSE 0 uint_16
Parameter Lists VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark 87
5 5