16-11 Power [hp]
Range: Function:
0.00 hp* [0.00 - 1000.00
hp]
View the DC link power in hp. The
value shown is calculated on the basis
of the actual motor voltage and motor
current.
16-12 Motor Voltage
Range: Function:
0.0 V* [0.0 - 65535.0 V] View the motor voltage, a calculated
value used for controlling the motor.
16-13 Frequency
Range: Function:
0.0 Hz* [0.0 - 6553.5 Hz] View the motor frequency, without
resonance dampening.
16-14 Motor Current
Range: Function:
0.00 A* [0.00 - 655.35 A] View the motor current measured as a
mean value, IRMS.
16-15 Frequency [%]
Range: Function:
0.0 %* [0.0 - 6553.5
%]
View a two-byte word reporting the actual
motor frequency (without resonance
dampening) as a percentage (scale
0000-4000 Hex) of 4-19 Max Output
Frequency.
16-18 Motor Thermal
Range: Function:
0.0 %* [0.0 - 100.0
%]
View the calculated motor temperature in
percentage of allowed maximum. At 100% a
trip will occur, if selected in 1-90 Motor
Thermal Protection. The basis for the
calculation is the ETR function selected in
1-90 Motor Thermal Protection.
3.12.3 16-3* Drive Status
16-30 DC Link Voltage
Range: Function:
0 V* [0 - 65535 V] View a measured value.
16-34 Heatsink Temp.
Range: Function:
0 C* [0 - 255 C] View the temperature of the frequency
converters heat sink.
16-35 Inverter Thermal
Range: Function:
0.0 %* [0.0 - 255.0 %] View the percentage of thermal load on
the frequency converter. At 100% a trip
will occur.
16-36 Inv. Nom. Current
Range: Function:
0.0 A* [0.0 - 655.35 A] View the inverter nominal current, which
should match the nameplate data on the
connected motor. The data are used for
motor protection, etc.
16-37 Inv. Max. Current
Range: Function:
0.0 A* [0.0 - 655.35 A] View the inverter maximum current. The
data are used for calculation of
frequency converter protection, etc.
16-38 SL Controller State
Range: Function:
0 * [0 - 255 ] View the actual state of the Smart Logic Controller
(SLC).
3.12.4 16-5* Ref. & Feedb.
16-50 External Reference
Range: Function:
0.0 %* [-200.0 - 200.0 %] View the total reference, the sum of
digital, analog, preset, bus and freeze
references.
16-52 Feedback[Unit]
Range: Function:
0.0
ProcessCtrlUnit*
[-4999.0 - 4999.0
ProcessCtrlUnit]
View the feedback
resulting from the
selection of scaling in
3-02 Minimum Reference
and 3-03 Maximum
Reference.
Parameters VLT HVAC Basic Drive Programming Guide
64 MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
3
3