Danfoss AME 35 Manual de usuario Pagina 5

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 28
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 4
55
Function test
The indicator light shows whether the
positioner is in operation or not. Moreover,
the indicator shows the control status and
faults.
Constant light
- normal operation
No light
- no operation or no power supply
Intermittent light (1 Hz)
- self adjusting-mode
Intermittent light (3 Hz):
- power supply too low
- insufficient valve stroke (<20 s)
- end-position cannot be reached.
Dimensions
Installation Guide AME 25, AME 35
Danfoss Heating EI.96.A9.2V DH-SMT/SI
Vista de pagina 4
1 2 3 4 5 6 7 8 9 10 ... 27 28

Comentarios a estos manuales

Sin comentarios