VLT
®
5000 FLUX
Appendix
The frequency converter is protected against short-circuiting on motor terminals U, V, W.
The frequency converter is protected against earth fault on motor terminals U, V, W.
Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if the intermediate circuit voltage becomes
too high or too low.
If a motor phase is missing, the frequency converter cuts out, see parameter 234 Motor phase monitor.
If there is a mains fault, the frequency converter is able to carry out a controlled decelleration.
If a mains phase is missing, the frequency converter will cut out when a load is placed on the motor.
MG.55.A7.02 - VLT is a registered Danfoss trademark
145