VLT
®
5000 FLUX
Programming
470 Adaptive Gain Scale
(ADAPTIVE GAIN)
Value:
20%-500%
100%
Function:
In many applications there is a need for having a
different tuning of the speed controller depending on
motor-speed; a high gain at low speeds (precise) and
a lower gain at high speed (smooth). This Parameter
defines a scaling of the proportional gain of the
speed controller (Par. 417) at low speed..
471 Adaptive Gain Min. Speed
(AG MIN SPEED)
Value:
0-1500 RPM
50 RPM
Function:
In many applications there is a need for having a
different turning of the speed controller depending on
motor-speed; a high gain at low speeds (precise) and
a lower gain at high speed (smooth). This Parameter
defines the minimum speed of the speed range
where adaptive gain scale is faded towards 100%
of the value entered in Parameter 417.
472 Adaptive Gain Max. Speed
(AG MAX SPEED)
Value:
0-1500 RPM
50 RPM
Function:
In many applications there is a need for having a
different tuning of the speed controller depending on
motor-speed; a high gain at low speeds (precise) and
a lower gain at high speed (smooth). This Parameter
defines the maximum speed of the speed range
where adaptive gain scale is faded towards 100%
of the value entered in Parameter 417.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A7.02 - VLT is a registered Danfoss trademark
109