Vista de pagina 96
InstallationGuideECLComfort210/310,applicationA214/A314
5.8Controlparameters(1)
Motorpr.(motorprotection)
11174
CircuitSettingrange
Factorysetting
1
OFF/10...59mOFF
Preventsthecontrollerfromunstabletemperaturecontrol(andresulting
actuatoroscillations).Thiscanoccuratverylowload.Themotorprotection
increasesthelifetimeofallinvolvedcomponents.
OFF:

10...59:



Xp(proportionalband)
11184
CircuitSettingrange
Factorysetting
1
5...250K80K


Tn(integrationtimeconstant)
11185
CircuitSettingrange
Factorysetting
1
1...999s30s




Mrun(runningtimeofthemotorizedcontrolvalve)
11186
CircuitSettingrange
Factorysetting
1
5...250s30s




Howtocalculatetherunningtimeofamotorizedcontrolvalve


Seatedvalves


Example:
5.0mmx15sec./mm=75sec.
Rotatingvalves


Example:90degr.x2sec./degr.=180sec.


