Frequency converter PK75 P1K5 PK2K2 PK3KO PK4KO PK5K5 PK7K5 PK11K PK15K P18K P22K P30K P37K P45K P55K P75K P90K
Estimated power loss [W], Best case/typical
1)
21716 46/57 46/58 66/83 95/118 104/13
1
159/19
8
242 330 396 496 734 705 927 1075 1425 1469
Weight enclosure IP54kg] 5.3 5.3 5.3 5.3 5.3 7.2 7.2 23 23 23 27 27 27 45 45 65 65
Efficiency [%], Best case/Typical 1 98.0/97.
6
97.7/97.
2
98.3/97.
9
98.2/97.
8
98.0/97.
6
98.4/98.
0
98.2/97.
8
98 98 98 98.0 97.8 98.3 98.3 98.3 98.3 98.5
Output current
50°C ambient temperature
Continuous (3 x
380-440 V) [A]
1.93 3.7 4.85 6.3 8.4 10.9 14.0 19.2 25.6 30 35.2 48.8 58.4 63.0 74.2 102.9 123.9
Intermittent (3 x
380-440 V) [A]
2.1 4.07 5.4 6.9 9.2 12.0 15.4 21.2 28.2 33 38.7 53.9 64.2 69.3 81.6 113.2 136.3
Continuous (3 x
440-480 V) [A]
1.8 3.4 4.4 5.5 7.5 10.0 12.6 16.8 21.6 27.2 32.0 41.6 52.0 56.0 73.5 91.0 112.0
Intermittent (3 x
440-480 V) [A]
2.0 3.7 4.8 6.1 8.3 11.0 13.9 18.5 23.8 30 35.2 45.8 57.2 61.6 80.9 100.1 123.2