Danfoss VLT 6000 Manual de usuario Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 23
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
VLT
®
6000 HVAC
MD.60.A2.02 - VLT is a registered Danfoss trademark
12
LC filters 6002-6006, 200 - 240 V / 6002-6011 380 - 460 V
The drawing on the left gives the measurements of
IP 20 LC filters for the above-mentioned power
range.
Min. space above and under enclosure: 100 mm.
IP 20 LC filters have been designed for side-by-side
installation without any space between enclosures.
Max. motor cable length:
- 150 m screened/armoured cable
- 300 m unscreened/unarmoured cable
If EMC standards are to be complied with:
- EN 55011-1B: Max. 50 screened/armoured cable
Bookstyle: Max. 20 m screened/armoured cable
- EN 55011-1A: Max. 150 m screened/armoured cable
Weight: 175Z0825 7.5 kg
175Z0826 9.5 kg
175Z0832 9.5 kg
Installation of LC filter IP 20 Bookstyle
Installation of LC filter IP 20
LC filter
LC filter
VLT
VLT
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 22 23

Comentarios a estos manuales

Sin comentarios