Danfoss FC 100 Series Instrucciones de operaciones Pagina 13

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 82
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 12
2. How to Install
2.1. Cabling
2.1.1. Cable Lengths
Baud rate Max total cable
length
Drop length
Maximum per drop Cumulative maxi-
mum
125k baud 500 meters (1640 ft.) 6 meters (20 ft.) for one drop 156 meters (512 ft.)
250k baud 250 meters (820 ft.) 78 meters (256 ft.)
500k baud 100 meters (328 ft.) 39 meters (128 ft.)
2.1.2. Cable Specifications
The cable used should be according to ODVA
specifications.
Be aware that the ODVA “Flat Cable” is an
unscreened cable type, and is not suited for
use with frequency converters.
Illustration 2.1: ODVA “Thin Cable” cross sec-
tion
FC 100/ 200/ 300 DeviceNet 2. How to Install
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
13
2
Vista de pagina 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 81 82

Comentarios a estos manuales

Sin comentarios